Set Up and Calibration Procedures 
Relays Set Up Group 
Revision 7 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
45 
7/08  
 
 
Table 14 Relay Type Descriptions 
When this Relay Type is 
selected… 
(RTYP) 
 
The Relay can be set up to indicate … 
 
Input Range 
The upper / lower limits of the input signal have been exceeded.   
Relay value parameter defines range limits and units are in percent of full span.   
Position Range 
Upper / lower limits of motor position have been exceeded.   
 Relay value parameter defines range limits and units are in either percent of 
span or degrees of rotation. See “Relay Examples “for setting range limits.  
Deviation 
Motor position has exceeded deviation limit from input. (Deviation is defined as: 
setpoint – motor position = Deviation) 
Relay value parameter defines limits and units are in percent of span.  
See “Relay Examples” for setting deviation limit. 
Upper Limit Travel 
The motor position has exceeded the upper limit of travel.   
(Same as Position Range.)  
Relay value parameter defines limits and units are in degrees of rotation or 
percent of span. See “Relay Examples” for setting upper limit with hysteresis. 
Lower Limit Travel 
The motor position has exceeded the lower limit of travel.  
(Same as Position Range.)  
Relay value parameter defines limits and units are in degrees of rotation or 
percent of span. 
Temperature High 
The high temperature limit of the actuator has been exceeded.  Relay value 
parameter defines temperature limits and units are in either degrees C or 
degrees F. 
(Temperature units are defined in the UNITS setting of the DISPLA set up 
group.) 
Temperature Low 
The low temperature limit of the actuator has been exceeded.  Relay value 
parameter defines temperature limits and units are in either degrees C or 
degrees F. 
(Temperature units are defined in the UNITS setting of the DISPLA set up 
group.) 
Starts 
The accumulated motor starts have exceeded the limit.   Relay value parameter 
defines the limit.  See “Relay Examples” for setting motor starts limit.  Range is 
from 10 to 99,990,000.    
Stall 
The motor is in a stall condition.   
Manual Mode 
The actuator is in manual mode.  
Power Up Test Failure 
A failure of any one of the power up test diagnostics.  See READ STATUS set up 
group.   
Failsafe 
The actuator is in failsafe. (input signal loss or input signal out of valid range) 
Position Sensor Failure 
The potentiometer or non-contact sensor output is out of range or has failed.   
Digital Input 
The digital input closure.   
Total Degrees 
The total degrees traveled.