Set Up and Calibration Procedures 
Relays Set Up Group 
Revision 7 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
47 
7/08  
 
 
Relay Type - Deviation  
Setting up a relay to alarm (energize) when the motor position deviates 10% (+ or -) from the actuator 
setpoint can be set up as follows.    
Set Up Group 
Parameter 
Value 
SET RELAY1 
RTYP11 
DEV 
 R11VAL 
10.00 
 R11HL 
HI 
 RTYP12 
DEV 
 R12VAL 
-10.00 
 R12HL 
LO 
 RLY1HY 
0.0 
The resulting action is shown below. 
100%
0%
Closed
-10%
RELAY n
Normally Open
Closed
Open
Motor
Position
Input
50%
+10%