Honeywell herculine 2000 User Manual

Page of 128
Set Up and Calibration Procedures 
Relays Set Up Group 
48 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
Revision 7 
  
 
7/08 
Relay Type – Upper Limit Travel with Hysteresis 
Selecting relay type ULim will cause the relay to energize when the motor position exceeds the upper limit 
trip point, and can be set up as follows.  Note that relay hysteresis parameter (RLY1HY) value is set to 10, 
which is 10% of range.  This means that when the relay is energized, due to the motor position exceeding 
the upper limit value, the relay will not de-energize until the motor moves to 10% below the trip point.  
Set Up Group 
Parameter 
Value 
SET RELAY2 
RTYP21 
ULim 
 R21VAL 
70.0 
 R21HL 
HI 
 RTYP22 
NONE 
 RLY2HY 
10.0 
 
100%
0%
Closed
70%
RELAY n
Normally Open
Motor
Position
60%
100%
0%
Closed
70%
RELAY n
Normally Open
Open
Motor
Position
60%H
y
s
t
e
r
e
s
I
s
H
y
s
t
e
r
e
s
I
s
Open
 
Relay Type – Motor Starts  
Selecting relay type STRT will cause the relay to trip when the number of motor starts exceeds the selected 
limit.  The motor starts value is stored as one of the maintenance group statistics.  This example sets the 
motor starts limit at 200,000 for Relay 1.   
Set Up Group 
Parameter 
Value 
SET RELAY1 
RTYP11 
STRT 
 R11 
E* 
X10K 
 R11VAL 
20 
 R11HL 
HI 
 RTYP12 
NONE 
The resulting action is that Relay 1 will trip when the number of accumulated motor starts in the 
maintenance group exceeds 200,000.