Set Up and Calibration Procedures 
Digital Input Set Up Group 
Revision 7 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
51 
7/08  
 
 
Digital Input Set Up Group 
Table 17 lists the parameters and selections availible for the SET DIGINP group.  
Table 17 Digital Input Set Up Group Parameters 
Actuator Lower 
Display 
Prompt 
Selections or 
Range of Setting  
Parameter Definition/PDA HercuLink
®
 Prompt 
DIGINP 
 
 
NONE 
UP 
DOWN 
USER  
default = UP 
Digital Input State
 Selects the position of the actuator in 
response to a digital input signal (contact closure).  
None
— No action by the actuator. 
Up
— Actuator motor moves to full scale value. 
Down
— Actuator motor moves to zero value. 
User
 selected value— Actuator motor moves to a 
customer-selected value.  
* Allows setting of End Position Value.  
EndPos 
0 – 100 
(in percent) 
END POSITION VALUE
— (DIGINP USER only) Selects the 
motor position you want the actuator to go to when digital 
input signal present (contact closure).