Set Up and Calibration Procedures 
Lock Set Up Group 
Revision 7 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
53 
7/08  
 
 
Lock Set Up Group 
Table 19 lists the parameters and selections available for the SET LOCK group. 
Table 19 Lock Set Up Group Parameters 
Actuator Lower 
Display 
Prompt 
Selections or 
Range of Setting  
Parameter Definition/PDA HercuLink
®
 Prompt 
LOCKID 
 0 to 4095 
 
default = 0 
PASSWORD LOCK
 4-digit password can be selected to 
provide security access to calibration information, set up 
parameters and supervisory functions. Password can be a 
number from 0 to 4095.  
 
LOCK 
 
 
NONE 
 
 
CAL 
 
 
CONF 
 
 
FULL 
default = NONE 
LOCK OUT FEATURE
— Selects lockout security for 
calibration and supervisory functions, and set up groups.     
None
— No lockout of any calibration or set up groups.  You 
select and change set up group values, and perform field 
calibration. 
Calibration
— Lockout for calibration groups SET CALINP, 
SET CALMTR, SET CALOUT and CAL POSOUT only.  You 
can select and change set up group values. 
Configuration
— Lockout for calibration groups and set up 
group configuration.  You can only scroll through and view 
set up group values.   
Full
— Lockout for calibration and all set up group values.  
Only SET LOCK and READ STATUS groups are accessible.  
MAENAB 
 
 
DIS 
ENAB 
default = ENAB 
Manual / Auto
— Allows the ability to lockout mode changes 
from the front panel. 
Disabled
— Disables the front panel auto / manual switch 
functionality. 
Enabled
— Enables the front panel auto / manual switch 
functionality.