Set Up and Calibration Procedures 
Maintenance Set Up Group 
60 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
Revision 7 
  
 
7/08 
Actuator Lower 
Display 
Prompt 
Selections or 
Range of Setting  
Parameter Definition/PDA HercuLink
®
 Prompt 
PDA users: The prompts are organized differently on your PDA’s 
HercuLink
®
 
software. Grayed prompts are under Configuration, Maintenance. Non-grayed 
prompts are under Maintenance.
 
DATSAV 
 
DIS 
ENAB 
MAINTENANCE DATA FORCED SAVE
— Allows you to 
manually force a save of the current maintenance data 
values. 
DISABLE
— Forced data save is disabled. 
ENABLE
— Forced data save is enabled. 
PASSWRD 
nnnn 
PASSWORD
 If a password has been activated, then a 4-
digit password is required to enable any of the functions 
below.   
NOTE:  Password is set (or changed) from the Lock set up 
group. 
MANRST 
 
 
NONE 
STAL 
STRT 
 
REGNn 
n
 = 0 to 9 
TEMP 
 
TDEG 
 
REL
n
 = 1, 2, 3 or 4 
ALL 
SYST 
default = NONE 
MAINTENANCE STATISTIC RESET
 Allows reset of the 
following maintenance statistics:  
None
— No reset of maintenance statisitics 
Stall
— Resets accumulated stall time to zero. 
Motor Starts
— Resets the accumulated motor start counter 
to zero. 
Motor Starts in the Region
— Resets the selected motor 
span region counter to zero.  
Temperature Statistics
— Resets the high / low 
temperature limit statistics. 
Total Degrees
— Resets the total degrees of motor travel to 
zero.   
Relay Counts
— Resets the selected accumulated relay 
cycle counter to zero. 
All
— Resets all maintenance statistics to zero. 
SYST
— Enables the system restart function.