Set Up and Calibration Procedures 
 
Revision 7 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
61 
7/08  
 
 
Actuator Lower 
Display 
Prompt 
Selections or 
Range of Setting  
Parameter Definition/PDA HercuLink
®
 Prompt 
PDA users: The prompts are organized differently on your PDA’s 
HercuLink
®
 
software. Grayed prompts are under Configuration, Maintenance. Non-grayed 
prompts are under Maintenance.
 
LD CAL 
NONE 
INP 
MTR 
COUT 
ALL 
POS 
 
 
 
default = NONE 
RESTORE CALIBRATION TYPE
— Allows you to restore a 
calbration value to its factory calibration. 
Input 
— Restores input calibration to the factory calibration    
for the current configured input type. 
Motor
— Restores motor calibration to the factory calibration. 
Output 
— Restores actuator output calibration to the factory    
calibration for the current configured output type. 
All 
— Restores input (for the type configured), motor and         
output (for the type configured) calibration to the factory 
calibration.   
POS 
— Allows a position sensor field calibration to be stored 
as a factory calibration. This is to be used when a sensor is 
replaced in the field.  See “Calibrate POS Output”.  
LD CFG 
DIS 
ENAB 
 
default = DIS 
RESTORE DEFAULT FACTORY CONFIGURATION
— 
Allows you to restore the factory default configuration. 
DIS 
— Restore disabled. 
ENAB
— Restore enabled. 
RESTRT DIS 
ENAB 
 
default = DIS 
SYSTEM RESTART
— Allows you to force the system to 
restart. 
DIS 
— Restart disabled. 
ENAB
— Restart enabled. 
Note: The MANRST function must be set to SYST
*  Temperature units are displayed in degrees C or F, and are set by the UNITS parameter.  See SET 
    DISPLA set up group. 
†  Note that the upper display contains the parameter name and the lower display contains the value.   
     This is to allow for the display of hours: minutes: seconds.