Set Up and Calibration Procedures 
Calibration 
Revision 7 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
71 
7/08  
 
 
Calibrate Output 
HercuLine
®
 2001/2002 actuator can be one of three output types: 
1.  0 to 20 mA, or 4 to 20 mA output 
2.  0 to 5 Volts, or 1 to 5 Volts with 250 ohm range resistor  
3.  Slidewire emulation.   
The output signal range is selected through the Current Out set up group using the keypad and local 
display.   
0/4-20 mA Output  
The HercuLine
®
 2001/2002 Actuator comes already calibrated from the factory.  If it becomes necessary to 
do a calibration in the field, adjust the output using the procedure in Table 27.  Refer to Figure 25 for a 
diagram to connect a signal source to the actuator input and a DVM to measure actuator output signal.   
This procedure provides the steps to calibrate the actuator for a 4 to 20mA output.  If you are using another 
output type, change the procedure accordingly.   
 
 
ATTENTION 
For an output calibration to be saved, you must complete the procedure.  The calibration will 
not be saved if you exit without completing the steps of the procedure.   
To exit calibation mode, press DISPLAY or SETUP keys. 
 
Table 27 Output Calibration Procedure 
 
Step 
Operation 
Press 
Result 
Enter Calibration 
Mode 
SETUP 
until you see 
Upper Display
 =   
CAL
 
Lower Display
  =  
CUR OUT 
 
 
 FUNCTION 
Upper Display
 =   
DIS
 
Lower Display
  =  
CALOUT 
 
 
 
 or 
 key 
Upper Display
 =   
BEGN
 
Lower Display
  =  
CALOUT