Set Up and Calibration Procedures 
Calibration 
72 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
Revision 7 
  
 
7/08 
Step 
Operation 
Press 
Result 
Calibrate Zero (0%) 
FUNCTION 
Upper Display =   
xxx
 
Lower Display  =  
ZERO 
• 
Read meter connected to actuator output. 
 
 
 
 or 
 key 
• 
Adjust actuator output to a value equal to 0% output as read 
from the DVM.   
NOTE:  Typically for a 4 mA output, the display will show a value 
of approximately 382.  A lower limit value is imposed on the zero 
output.  If the value is 357 or lower, the actuator will not allow you 
to calibrate the zero output.  The value must be larger than 357 
for a valid calibration.   
Calibrate Span 
(100%) 
FUNCTION 
Upper Display
 =   
xxxx
 
Lower Display
  =  
SPAN 
• 
Read meter connected to actuator output. 
 
 
 
 or 
 key 
• 
Adjust actuator output to a value equal to 100% output as read 
from the DVM.   
• 
NOTE:  Typically for a 20 mA output, the display will show a 
value of approximately 1887. 
 
 FUNCTION 
Calibration for zero and span output values are now stored.  
Output calibration is complete.   
 
Slidewire Emulation  
The HercuLine
®
 2001/2002 Actuator comes already calibrated from the factory. If it becomes necessary to 
do a calibrationin the field, adjust the output using the procedure in Table 28. Refer to Figure 26 for a 
diagram to connect a signal source to the actuator input and a DVM to measure actuator output signal. 
 
 
ATTENTION 
For a slidewire emulation output calibration to be saved, you must complete the procedure. 
The calibration will not be saved if you exit without completing the steps of the procedure.  
To exit calibration mode, press DISPLAY or SETUP keys.