Set Up and Calibration Procedures 
Setting Auxiliary Switches 
Revision 7 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
81 
7/08  
 
 
Setting Auxiliary Switches 
 
 
 
ATTENTION 
Referring to Figure 31.  The first two cams (starting from the front) are for the 0% and 
100% end of travel limit switches (Switches #1 and #2
) and should not need any 
adjustments as they are factory set to stop the actuator precisely at 0% and 100%. See 
Setting End-of-Travel Limit Switches (page 78). 
Additional switch settings should be set so that switch #3 operates in synchronism with switch 
#1 (i.e., both activating when the actuator is going in the same direction) and switch #4 to 
operates in synchronism with switch #2, etc.  See Figure 32 for auxiliary switch settings. 
 
 
SW #3
SW #4
NC
NC
100%
0%
20 (SW4 COM)
16
21
19
18
LEFT HAND
POINTER SCALE
SW #5
SW #6
24
25
22
27
NC
NC
NO
NO
NO
NO
23 (SW5 COM)
(SW 6 COM) 26
17 (SW3 COM)
 
 
Figure 32 Auxiliary Switch Settings 
 
If it becomes necessary to do adjust the auxillary switch cams in the field, use the procedure given in Table 
33. 
 
While the unit is powered, a potentially lethal shock hazard exists inside the case.