Set Up and Calibration Procedures 
Setting Auxiliary Switches 
82 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
Revision 7 
  
 
7/08 
Table 33 Auxiliary Switch Setting Procedure 
 
Step 
Action 
Remove AC power to the actuator. 
Remove the six screws and the cover from the actuator case.  See Figure 2.  Lay cover 
assembly on a flat surface. 
Using a flat blade screwdriver on the slots on edge of cams, or your fingers, rotate the cams 
until the switches are set. (See Figure 31)  
• 
The auxiliary switches should be set so switches #3 and #5 operate in synchronism with 
switch #1 (i.e., both activating when the drive is going in the same direction) and set 
switches #4 and #6 to operate in synchronism with switch #2.  See Figure 32 for auxiliary 
switch settings. 
For Switches #3 and #5: 
• 
Rotate the actuator shaft, using the manual handwheel or the auto-manual switch, to the 
desired low scale position. 
• 
Rotate the #3 switch operating cam to activate at this position.  The switch roller arm should 
go from being in an up, not depressed state, to a depressed state as the cam is rotated in 
the direction of the shaft rotation going toward the limit position. This will cause the switch to 
go from NC to NO and turn off the power to the motor when the switch activates.  Switch 
activation may be detected by the clicking sound or with a continuity tester connected to the 
terminals.  
• 
Repeat for Switch #5 if applicable. 
For Switches #4 and #6: 
• 
Rotate the actuator shaft, using the manual handwheel or the auto-manual switch, to the 
desired up scale position. 
• 
Rotate the #4 switch operating cam to activate at this position.  The switch roller arm should 
go from being in an up, not depressed state, to a depressed state as the cam is rotated in 
the direction of the shaft rotation going toward the limit position.  This will cause the switch 
to go from NC to NO and turn off the power to the motor when the switch activates. 
• 
Repeat for Switch #6 if applicable. 
Double check limit switch actuation by first manually driving the actuator to each end of travel 
and hearing the switch click or by detecting it with a continuity tester. Secondly, drive the 
actuator to both ends of travel (using the auto/manual switch or by providing minimum and full 
input signal) and make sure the switches activate and turn off the motor.