How to Recover From a Lost Password
You can use a local computer that connects to the Switched Rack PDU 
through the serial port on the front of the unit.
1. Select a serial port at a local computer, and disable any service that 
uses the port.
2. Use the configuration cable (940-0144) to connect the selected port 
to the serial port on the front panel of the PDU. 
3. Run a terminal program (such as HyperTerminal) and configure 
the selected port for 9600 bps, 8 data bits, no parity, 1 stop bit, and 
no flow control, and save the changes.
4. Press 
E
NTER
 to display the User Name prompt.
5. Press the Reset button on the Switched Rack PDU, which causes 
the Switched Rack PDU to restart, a process that typically takes 
approximately 15 seconds.
6. Press 
E
NTER
 as many times as necessary to redisplay the User 
Name prompt, then use apc for the user name and password. (If 
you take longer than 30 seconds to log on after the User Name 
prompt is redisplayed, you must start the login procedure again at 
step 4.)
7. From the Control Console menu, select System, then User 
Manager
8. Select Administrator, and change the User Name and Password 
settings, both of which are now defined as apc.
9. Press 
C
TRL
-C
 and log off.
Note
Reconnect any cable that you disconnected in step 2 and 
restart any service that you disabled in step 1.