APC Rack PDU AP7920 User Manual

Product codes
AP7920
Page of 24
14
Switched Rack PDU Installation and Quick-Start Manual
How to Download Firmware Updates
You can use a local computer that connects to the Switched Rack PDU 
through the serial port on the front of the unit.
1. Select a serial port at the local computer, and disable any service 
that uses that port.
2. Use the configuration cable (940-0144) to connect the selected port 
to the RJ-12 serial port on the front panel of the Switched Rack 
PDU.
3. Run a terminal program (such as HyperTerminal) and configure 
the selected port for 9600 bps, 8 data bits, no parity, 1 stop bit, and 
no flow control. Save the changes.
4. Press 
E
NTER
 twice to display the User Name prompt.
5. Enter your user name and password (both apc, for administrators 
only) and press 
E
NTER
.
6. From the Control Console menu, select System, then Tools, then 
XMODEM.
7. The system will prompt you with 
Perform transfer with
XMODEM -CRC?
 Type 
Yes
 and press 
E
NTER
.
8. The system will then prompt you to choose a transfer rate and to 
change your terminal settings to match the transfer rate. Press 
E
NTER
 to set the Switched Rack PDU to accept the download.
9. In the terminal program, send the file using the XMODEM 
protocol. Upon completion of the transfer, the console will prompt 
you to restore the baud rate to normal.
The Switched Rack PDU will reboot when the download is complete.
See also
For a complete description on how to download a firmware 
upgrade for your Switched Rack PDU, see the Addendum 
on the provided APC Switched Rack PDU Utility CD.
Caution
Do not interrupt the download.
Note
Upgrading the firmware will not interfere with the 
operation of the outlets.