Recommended Source Connections
 
1) Input electricity to be provided from a dedicated, grounded 4-wire WYE power supply source 
with a grounded neutral.
2) Ensure clockwise voltage phase rotation (L
 
1
 
,L
 
2
 
,L
 
3
 
).
3) All wire sizes must comply with national and local codes. 
 
Recommended Current Protection
 
4) Input; 100 Amp gL type current-limiting fuse on each input phase.
5) Output; 63 Amp 3-Pole AC circuit breaker or a 63 Amp gL fuse with 30kAIC.
 
Recommended Wiring for a 40°C Temperature Environment
 
6) Input cables: 35mm
 
2
 
. Output cables: 16 mm
 
2
 
. External PE cable: 16 mm
 
2
 
Refer also to local electrical regulations.
7) Neutral Output Wires; rate for 173% of output phase current if feeding all Switch Mode Power 
Supply loads without power factor correction. 
 
4
 
Wall Fitting
 
Figure 4.1
 
5
 
 Wiring Overview
 
6
 
Input/Output Wiring
 
 Make sure unit is in its location of use before wiring begins.
 Loosen screws to remove plate.
 
 Punch holes as required and reinstall panel before mounting wiring hardware.
 
7
 
Connecting the UPS to the MBP
 
Output Voltage (on line)
3-Phase 
 380V     400V     415V   
Output Current (nominal, per phase)
 61A       58A       56A
Maximum Output Current
(in bypass only at 125% overload, per phase)
   76 A
Neutral Output Current (with 100% switch mode load)
106A     100A      96A 
*note 7
Output Current Protection (external to enclosure, not supplied)
63A *note 5
B
A
Weight of MBP: 30 kg.
4 x ø 8.5 mm
.
Fixing holes in rear box
POWER
INTERFACE WIRING
SYMMETRA PX
Input
Power
Output
Power
EPO
MAINTENANCE
BYPASS PANEL
X001
SYSTEM INPUT
UPS INPUT
UPS OUTPUT
X004
SYSTEM OUTPUT
N
L1
L2
L3
N
L1
L2
L2
L3
N
L1
L3
Connect UPS Input and Output power.
Connect System Input and Output.
Connect Maintenance Bypass Panel control wiring, X010.
1
2
3
2
2
1
1
3
Rear Wiring
Bottom Wiring
1
1
2
1
2
1
2
J6
J1
J3
Emergency Power 
OFF Switch Keep 
EPO wire routing 
isolated and 
use separate 
EPO conduit
AC
Output
AC
Input
DC Input
(Optional XR)
1/2
  Q001 UPS input switch (N/O position)
3/4
  Q002 UPS output switch (N/O position)
5/6
  Q003 UPS service bypass switch 
(N/C position)
7/8
  OK to operate UPS Output switch Q002
9/10
 OK to operate service bypass switch 
Q003
11/12
 Not used
13/14
 External Switch Gear present
4
 Ground
N/O EPO Control
N/C EPO Control
3/2 
Relay Coil 1
1
 Internal 
Power
+24V Supply
8
 Ground
7/6
  Relay Coil 2
5
 Internal 
Power
+24V Supply
Connect power input and output wiring to terminals 
as shown. Route Input and Output in separate 
conduits.
Make Ground connections as shown. Feed ground 
wire through Ferrite beads provided.
Connect EPO as shown schematically in Section 5.
Connect MBP as shown.
Emergency shut-down 
with internal supply
CAUTION!
Ensure clockwise phase
rotation and neutral location
CAUTION!
Ensure clockwise phase
rotation and neutral location
Input/Output Wiring of Maintenance Bypass 
Panel (MBP)
Input signals: Contact load: TTL
Output Relays:
3
2
1
1
4
1
2
3
4
0.3VA/1.9kW
240V/8A
Power Terminal Lug Diameter is 8 mm,
Torque Value: 6Nm.
Wiring Steps