APC BX1500G User Manual
Installation and Operation Back-UPS BX1300G/BN1350G/BX1500G
6
Modes of operation
Press
D
ISPLAY
to scroll through the display screens.
Status indicators
System faults
On Line Mode
On Battery Mode
Input Voltage
Estimated runtime in minutes
Counter
Power Event Counter
Estimated run time
Output Voltage
Load in Watts
Input Voltage
Load in %
Load in Watts
Output Voltage
Load in %
Output Frequency
Output Frequency
Status
LED
Audible Alarms
Audible Alarm Terminates
Overload
An overload condition has occurred
while operating on AC or battery power.
An overload condition has occurred
while operating on AC or battery power.
Constant tone
The alarm stops when nonessential
equipment is disconnected from the
Battery Backup outlets or the Back-UPS
is turned off.
equipment is disconnected from the
Battery Backup outlets or the Back-UPS
is turned off.
On Battery
The Back-UPS is supplying battery
power to the Battery Backup outlets.
The Back-UPS is supplying battery
power to the Battery Backup outlets.
Beeps 4 times every 30
seconds.
The beeping stops when AC power is
restored or the Back-UPS is turned off.
restored or the Back-UPS is turned off.
Low Battery
The Back-UPS is supplying battery
power to the Battery Backup outlets and
the battery is near a total discharge state.
The Back-UPS is supplying battery
power to the Battery Backup outlets and
the battery is near a total discharge state.
Continuous beeping
The beeping stops when AC power is
restored or the Back-UPS is turned off.
restored or the Back-UPS is turned off.
F01
On-Battery Overload
Turn the Back-UPS off. Disconnect non-essential
equipment from the Battery Backup outlets and then
turn Back-UPS on.
equipment from the Battery Backup outlets and then
turn Back-UPS on.
F02
On-Battery Output Short
Turn the Back-UPS off. Disconnect non-essential
equipment from the Battery Backup outlets and then
turn Back-UPS on.
equipment from the Battery Backup outlets and then
turn Back-UPS on.
F03
On-Battery Xcap Overload
Faults F03-F09 are not user serviceable. Contact APC
Technical Support for assistance.
Technical Support for assistance.
F04
Clamp Short
F05
Charge Fault
F06
Relay Welding
F07
Temperature
F08
Fan Fault
F09
Internal Fault