LA-ITR-LCD
 
 
Technical Specifications 
 
ITR-LCD SERIES – HIGH PERFORMANCE LINE-INTERACTIVE UPS 
 
MODEL 
LA-ITR-800 
LCD 
LA-ITR-1100 
LCD 
LA-ITR-1500 
LCD
 
LA-ITR-2000 
LCD
 
LA-ITR-2500 
LCD
 
LA-ITR-3000 
LCD 
CAPACITY 
800VA/640W  1100VA/880W  1500VA/1200W 2000VA/1600W 2500VA/2000W 3000VA/2400W 
INPUT 
Voltage  
110/120VAC or 208/220/230/240VAC 
Acceptable Voltage Range 
81-145VAC  /   162-290VAC 
Frequency Range 
60/50 Hz (auto sensing) 
OUTPUT 
Voltage regulation (AC Mode) 
110/120VAC or 208/220/230/240VAC 
Voltage regulation (Battery Mode) 
±1% 
Frequency Range (Battery Mode) 
60 Hz or 50 Hz  ±1 Hz 
Current Crest Ratio 
3:1 
Harmonic Distortion 
5% max. @ 100% linear load, 10% máx. @ 100% non-linear load (before alarm) 
Transfer time 
Typical 2-6 ms, 10ms max. 
Waveform (Battery Mode) 
Pure Sine Wave 
BATTERY 
Type 
Number 
12V/7AHx2 12V/9AHx2 12V/7AHx4 12V/9AHx4 12V/7AHx6 12V/9AHx6 
Charging Volt. 
27.4 VDC 
±1% 54.8 
VDC 
±1%
 
82.1 VDC 
±1% 
Backup time 
10 min. 
10 min 
13 min 
13 min 
14 min 
12 min 
Standard Model 
Typical 
Recharge time  
4 hours recover to 90% capacity 
Charging current 
4A / 8A 
4A / 8A 
4A / 8A 
Long-run Model 
Charging Volt. 
 
27.4 
VDC
 
±1% 
 
54.8 
VDC
 
±1% 
 
82.1 
VDC
 
±1% 
INDICATORS 
LCD  Display 
AC mode, Battery mode, Load level, Battery level, Input Voltage, Output Voltage, Overload, 
Fault and Low battery 
PROTECTION 
Full Protection 
Overload, discharge and overcharge protection 
ALARM 
Battery Mode 
Sounding every 10 seconds 
Low Battery 
  
Sounding every second 
Overload 
  
Sounding every 0,5 seconds 
Fault 
  
Continuously sounding 
INTERFACE 
Output connectors 
8 x IEC 
7 x IEC 
Communication ports 
1xUSB + 1xRS-232 + 1xRJ11 
PHYSICAL 
Dimensions, 
DxWxH (mm) 
380 x 438 x 88 
480 x 438 x 88 
600 x 438 x 88 
Standard Model 
Net Weight (Kg) 
12.9 
14.23 21.08 23.11 30.65 32.24 
Dimensions, 
DxWxH (mm) 
380 x 438 x 88
480 x 438 x 88 
600 x 438 x 88
Long-run Model 
Net Weight (Kg) 
 
10.8 
 
14 
 
18 
ENVIRONMENT  
Humidity 
  
0-90 % RH @ 0 - 40°C (non condensing) 
Noise Level 
Less than 45dB 
MANAGEMENT 
RS-232 & USB  
Supports Windows® 2000/2003/XP/Vista/2008/7, Linux, Unix and MAC 
Optional SNMP 
Power management from SNMP manager and web browser
 
* Specifications are subject to change without further notice 
 
 
 
 
 
- 16 -