Janitza Prodata 2 5224001 Data Sheet

Product codes
5224001
Page of 56
31
ProData II
Pulse counters
All digital inputs can be operated with a frequency of 
25 Hz. Here, the pulse duration and the pulse interval 
must be greater than 20 ms. The typical pulse duration 
for S0 pulses is 30 ms.
The maximum number of pulses per hour is based on 
the minimum pulse duration and the minimum pulse 
interval:
Pulse duration 
> 20 ms
Pulse interval 
> 20 ms
Examples of the maximum possible number of pulses 
per hour.
Pulse length
Pulse interval
Max. pulse/h
20 ms
20 ms
90 000 pulse/h
30 ms
30 ms
60 000 pulse/h
50 ms
50 ms
36 000 pulse/h
100 ms
100 ms
18 000 pulse/h
500 ms
500 ms
3600 pulse/h
1 s
1 s
1800 pulse/h
10 s
10 s
180 pulse/h
The pulse counters can be configured with 
a simultaneous measurement value or power calculation. 
The pulses are counted as 64-bit numbers and overflow 
after approximately 1.17 x 10
10
 years of continuous 
operation (25 Hz).
Pulse value:
A pulse value can be assigned to each digital input. 
Use the impulse value to specify the measurement value 
or power value (e.g. energy) to which a pulse should 
correspond.
Measurement value calculation:
Power value calculation:
Measurement value = pulse x pulse value
Power value =
pulse x pulse value
Time [sec]