Janitza Prodata 2 5224001 Data Sheet

Product codes
5224001
Page of 56
34
ProData II
Clock
The internal device clock is recorded in UTC (Universal 
Time Coordinated) format with a resolution of 1 second 
and converted into the local time via a possible 
configuration of the time zone and the switch between 
daylight saving time and standard time. 
The time can be read and set via a Modbus address. 
The GridVis software can be used as a user-friendly way 
to set the clock.
A minute or hour synchronisation of the time takes place 
via digital input 9. 
Example:
When synchronising the time via Ethernet (NTP), 
the external clock is only set and is read during a restart. 
The NTP service can receive broadcasts (passive) or 
send queries to an NTP server (active). In active mode, 
an NTP server with the IP address must be set. A name 
resolution is not possible.
Current device time
Time after minute pulse
15:05:51
15:06:00
15:05:11
15:05:00
Current device time
Time after hour pulse
15:05:11
15:00:00
Timer
In the ProData 2, 64 independent weekly timers can be 
set; here, the resolution is 1 minute. The weekly timer 
defines an active period within a day; the active day 
must be released within a week.
Example of an active period: 
From 9:25 to 11:45 am Sunday, Monday and Friday
The weekly timers can be configured as tariff converters 
(1..8), setting digital outputs 1-3, but also as "inoperable". 
The status can always be queried via the Modbus. 
The states of the timer are linked via an OR operator to 
the digital output.
The weekly timer must be set using the GridVis software.