Janitza Prodata 2 5224001 Data Sheet
Product codes
5224001
35
ProData II
Recordings
Recordings with static access (SCADA systems):
• Differential monthly values (without tariff) and
the maximum power values are saved for each
digital input for the current and previous year.
digital input for the current and previous year.
• Static recordings such as work values of the pulse
inputs (pulse number x factor) and the minimum/
maximum values of the temperature input are
stored in the flash memory every 3 minutes.
maximum values of the temperature input are
stored in the flash memory every 3 minutes.
Recordings in the data flash (for GridVis software):
• Up to 8 recordings with up to 29 values can
be stored in the ProData 2.
• The smallest time basis for recordings is 1 minute
and the largest time basis is 60 min.
• Recordings and the names of the power values
can be adjusted and extended via the GridVis
software.
software.
Data memory
The size of the ProData 2's flash memory is 32 MB;
24 MB is available for recordings and 5 MB is available
for the cyclical drawings of the work values.
24 MB is available for recordings and 5 MB is available
for the cyclical drawings of the work values.
Recording all 15 channels at a recording interval of
15 minutes results in a recording depth of approximately
1024 days.
15 minutes results in a recording depth of approximately
1024 days.
The memory is read or deleted via a Modbus or via
the GridVis software.
the GridVis software.