15. REGULATORY INFORMATION 
Components 
 
 
VRLA Battery 
Required Markings: 
 
 
 
Crossed-out wheeled bin indi
cating “SEPARATE COLLECTION” for all 
batteries and accumulators.  Not to be disposed of with general domestic, 
commercial or industrial waste. 
Ref: The Batteries Directive 2006/66/EC 
 
 
The Pb symbol indicates the heavy metal content of the battery and enables 
the lead-acid battery to be sorted for recycling.  
Ref: The Batteries Directive 2006/66/EC. 
 
 
The International Recycling Symbol, required by law in many countries 
world-wide to facilitate the identification of secondary batteries and 
accumulators for recycling. 
Ref: IEC 61429 : 1995, Marking of secondary cells and batteries with the 
International Recycling Symbol ISO 7000-1135. 
 
16. OTHER INFORMATION 
Components 
 
VRLA Battery 
To ensure the safe use of VRLA Batteries supplied by Yuasa Battery (UK) Ltd., the following precautions must be 
observed: 
 
  Only trained, competent personnel, who have received special instructions for the hazards and risks, should be 
allowed to handle VRLA Batteries. 
 
  Never short-circuit battery terminals, since sparks and arcs produced can injure personnel and are a fire and 
explosion hazard. 
 
  VRLA Batteries emit hydrogen gas which is highly flammable and will form explosive mixtures in air from approx 
4% to 76%.  Never install VLRA Batteries in a gas-tight enclosure, whether during storage, transport or usage. 
 
  Batteries must always be charged on a voltage-regulated charging system with adequate ventilation provided to 
avoid the build-up of ignitable gases and to promote good heat dissipation. 
 
  Do not charge VLRA Batteries above + 50 ºC, discharge or store above + 60 ºC. 
 
  Under extreme conditions of charging equipment malfunction and/or battery failure, high voltage and high 
temperature conditions may occur causing the evolution of Hydrogen Sulphide (H
2
S) gas, which is toxic. If 
detected by its odour of rotten eggs (at extremely low concentrations), switch off the charging equipment, evacuate 
all personnel from the area and ventilate well. Seek advice before attempting to re-start charging.  
 
Risk Phrases 
R21 
Harmful in contact with skin 
 
R22 
Harmful if swallowed 
 
R23 
Toxic by inhalation 
 
R24 
Toxic in contact with skin 
 
R25 
Toxic if swallowed 
 
R35 
Causes severe burns 
 
R36 
Irritating to eyes 
 
R37 
Irritating to respiratory system 
 
R38 
Irritating to skin 
 
R49 
May cause cancer by inhalation 
 
R52 
Harmful to aquatic organisms 
 
R53 
May cause long-term adverse effects in the aquatic environment