This document details the Modbus RTU memory mapping that is implemented in the Versidrive E2 drives, 
detailing which addresses are used to read and write data to / from Versidrive E2 in a Modbus RTU network.  
 
Note that for E2 drive, once the Modbus control/monitor is enabled (P-36>0), the Versibus network function 
will be disabled, therefore disabling the Versipad E2 remote keypad and Versistick. 
 

For control & monitoring of the drives the following parameters should be set correctly:  
P-12 : (set to 3 for Modbus without ramp control or 4 for Modbus with ramp control ) 
P-36 : (communication address, baud rate and comms loss trip time)  
P-15 (Analog and Digital input configuration)  
 
For monitoring of the drives the following parameters should be set correctly: 
P-36 : (communication address, baud rate and comms loss trip time)  
P-15 (Analog and Digital input configuration) 
 
Please see User Guide for more information on these parameter settings  
The Fieldbus Gateways (Profibus, DeviceNet & Ethernet) also use the Modbus interface. In this case, the baud 
rate must be set to 57.6kbps. 
 
PETER electronic GmbH & Co. KG adopts a policy of continuous improvement and whilst every effort has been 
made to provide accurate and up to date information, the information contained in this document should be 
used for guidance purposes only and does not form the part of any contract. 
 
MODBUS RTU Protocol Specification  
The following table highlights the specification for the Modbus RTU implementation in E2  
Protocol  
Modbus RTU  
Error check  
CRC  
Baud rate (P-36)  
9600bps, 19200bps, 38400bps, 57600bps, 115200bps 
(default)  
Data format  
1 start bit, 8 data bits, 1 stop bits, no parity.  
Physical signal  
RS 485 (2-wire)  
 
Memory Map  
Table 1: Control and status registers  
Register  
Upper byte  
Lower Byte  
Command  
Type  
1*  
Command  
03,06  
Read/Write  
2*  
Speed reference  
03,06  
Read/Write  
3*  
Reserved  
03,06  
Read/Write  
4*  
Modbus ramp control time  
03,06  
Read/Write  
5  
Reserved  
03  
Read Only  
6*  
Error code  
Drive status  
03  
Read Only  
7*  
Motor speed  
03  
Read Only  
8*  
Motor current  
03  
Read Only  
9*  
Reserved  
03  
Read Only  
10  
Reserved  
03  
Read Only  
11  
Digital input status  
03  
Read Only  
12  
Rating ID  
03  
Read Only  
13  
Power rating  
03  
Read Only  
14  
Voltage rating  
03  
Read Only