Peter Electronic VD 075/E2 1-phase frequency inverter, to , 2I000.23075 2I000.23075 Data Sheet

Product codes
2I000.23075
Page of 6
Read only registers  
Register 6: Drive status and error code  
High byte gives drive error code. (Valid when drive tripped, see appendix for details)  
Low byte gives drive status (0: drive stopped, 1: drive running, 2: drive tipped)  
Register 7: Motor speed information  
This register gives motor speed information.  
The data is 16bits integer with one decimal place. E.g. value 123 gives 12.3Hz. Value -234 (0xFF16) gives -
23.4Hz.  
Register 8: Motor current  
This register gives motor current information.  
The data is 16bits integer with one decimal place. E.g. 156 = 15.6A, 12 = 1.2A.  
Register 11: Digital input status 
The value in this register represents the drive terminal digital input status (Digital input 1 to 4). Lowest bit 
indicates digital input 1 status. 
Register 12: Rating ID The value in this parameter includes specific drive ID information, and is not 
recommended to be used by customer. For more information regarding this parameter, please contact Invertek 
Drives Ltd directly.  
Register 13: Power rating This gives the drive power rating information, value includes two decimal places. The 
unit of this register depends on the drive type (KW/HP)  
Register 14: Voltage level This register gives the rated input voltage for the drive. i.e. 230 : 230V 400: 400V 460: 
460V  
Register 15: IO software version This register contains the drive IO software version info. Value includes two 
decimal places. i.e. 100 means version 1.00  
Register 16: Motor control processor software version This register contains the software version info of the 
motor control processor. Value includes two decimal places. E.g. 100 means version 1.00  
Register 17: Drive type This register gives drive internal type code.  
Register 20: Analog input 1 value This register gives drive analog input 1 value after scaling and offset control. 
Value 4096 = 100%.  
Register 21: Analog input 2 value This register gives drive analog input 2 value after scaling and offset control. 
Value 4096 = 100%.  
Register 22: Speed reference value This register contains the reference speed information that being used by 
the drive for motor speed control. The data is in Hz and with one decimal place ( i.e. 234 = 23.4Hz)  
Register 23: DC bus voltage This register contains drive internal DC bus voltage information. Data unit is Volt.  
Register 23: Drive temperature This register contains drive temperature information. Data is in Celsius with no 
decimal place.