t1F - time, during which the load relay will be open after de-energizing resulting from the watts input crossing 
the main threshold 
 
Figure 1.2 - OM-310 operation in the power limiting mode when 
=0, =1, =3 
 
 
1.2.5.3 Active power limiting during operation of a characterizing relay at 
= 2 ( relay used for connecting ad-
ditional load) 
After 
ОМ-310 energizing, after AR time (Att parameter) the load relay will close.  After the delay, defined by 
” or “” parameter (whichever time is longer), the characterizing relay closes while connecting additional load. 
If during operation the active power consumed by the load crosses the additional threshold (line 2 figure 1.3) for a 
time period that is longer than assigned by “
” parameter, the characterizing relay will open.   
Characterizing relay will re-close again: 
а) at  =0, after time, assigned by t2F parameter (instance of the characterizing relay closure - line “b” on 
fig.1.3.); 
b) at  
=1, when  load consumed power will reduce till the additional load power-on threshold (line  3 on 
fig.1.3) (the characterizing relay engaging point - line “a” on fig.1.3.); 
c) at  
=2 depending on which event (a or b) comes first. 
If during operation the active power consumed by the load crosses the additional threshold (line 1 figure 1.3) for 
a time period that is longer than assigned by “
” parameter, the characterizing relay and the load relay will open.  
The load relay and characterizing relay will be re-closed after AR period, or after time specified by 
 parame-
ter (whichever of the time periods is longer) (Figure 1.3). 
 
 
 
 
Load consumed input wattage 
 
 
 
 
 
 
 
 
 
Characterizing relay in the mode of controlling 
additional load 
 
 
 
Load relay 
 
 
 
1 – main threshold  (“
” parameter) 
2 – additional de-energize threshold  (“
” parameter) 
3 – additional energize threshold  (“
” parameter) 
 
Figure 1.3 - OM-310 operation in the power limiting mode when 
=2 
 
The wattages values for the main threshold, the additional threshold, and the additional load energize threshold  
depend on the “
” parameter value.  
When 
=0, the load consumed power is calculated for each phase separately and is compared with the thre-
sholds calculated as: 
Main threshold (kW) = (“Pnn” * “P1F”) /(100*3), where 
 “Pnn” – cumulative rated load wattage, kW; 
 “P1F” – main threshold, %. 
Additional threshold (kW) = (“Pnn” *  “P2F”) /( “100”*3), where 
“P2F” – additional threshold, %. 
 
When 
=1 the main threshold, the additional threshold and the energizing threshold are calculated similarly to 
the way described under paragraph 1.2.5.2