Novatek THREE-PHASE POWER LIMITER OM-310 OM-310 Data Sheet

Product codes
OM-310
Page of 28
- 13 - 
NOVATEK-ELECTRO
                                                                                                                                                       
ОМ-310
 
 
Figure 1.5 - Principle of protection with dependent time delay 
 
Graphs for the protection operation time constant equal to 1 sec (“


” parameter) are provided in Appendix 1. 
When a different value for time constant is set, the protection trip time changes proportionally to the time constant 
(for example, at “


”=10 seconds the protection trip time at the same current ratio will increase 10 times). 
 
1.2.6.4  Ground fault protection:  
- is activated when earth fault current reaches the trip threshold (“
”);parameter); 
 - the load relay opens if the earth fault current crosses the trip threshold within T time period (“
” parameter). 
1.2.6.5  Voltage based protection 
In voltage-based protections, before load energizing, OM -310 checks for corresponding threshold settings, and, 
depending on their value, either permits or prohibits load energization; after load energization the voltage control is 
retained. 
Voltage-based protections include: 
- protection for minimum line voltage (it trips when at least one of the line currents is less than the threshold set-
ting (“


” parameter) within time specified by “

” parameter);.  
- protection for maximum line voltage (it trips when at least one of the line currents is greater than the threshold 
setting (“


” parameter) within time specified by “

” parameter);  
- protection for line voltages imbalance ( trips if difference between RMS line voltages exceeds the set threshold 
(“

” parameter) within time assigned by “
” parameter). 
 
1.2.6.6  Protection based on phase sequence order trips in case of  phase sequence order fault or phase coin-
cidence it opens the load relay and locks its further operation. 
  
1.2.6.7 Starter unit operability control (at 
=1). If currrents are present when the relay is open, the starter is 
considered faulty. Further OM-310 operation is locked. The alarm reset can be performed by de-energizing only. 
 
1.3 PRODUCT PACKAGE CONTENTS 
The product package contents are shown in Table 1.7. 
 
Table 1.7 -  Product package contents 
 
Description 
Abbreviation 
ОМ-310 
ОМ-310 
Differential current transformer (zero sequence transformer)* 
 
Cable for communication with PC via RS-232*  
KC-01 
Transmitter cable for communication with PC via USB* 
KC-USB-01 
 
* - supplied optionally 
 
 
 
1.4 EQUIPMENT FEATURES AND OPERATION 
 
ОМ-310 is a microprocessor-based digital device that provides a high degree of reliability and accuracy. The 
device doesn't need any auxiliary supply: it's self-powered by the voltage to be monitored.  
 
ОМ-310  device is equipped with three built-in CTs, through which  power phase mains are conducted. 
 
 
2. INTENDED USE 
2.1. SAFETY 
All connections must be performed on dead device.  
 
2.2 ОМ-310 DEVICE CONTROL 
2.2.1 Control Modes 
OM-310 has five control modes: 
-keyboard lock level; 
- mode with minimal number of setting parameters (further on referred to as MMSP);   
-user level; 
-service engineer level; 
- remote control. 
In all operation modes the following features are available: 
- viewing measured and displayed parameters 
 
(Tablе 1.4). Scrolling through parameters list is performed by 
DOWN and UP buttons; 
-
faults log view (п.2.4.8).