Entes MKC-06 Phase failure relay MKC-06 MKC-06 Data Sheet

Product codes
MKC-06
Page of 2
PHASE FAILURE DEVICES
MKC-05, MKC-05P, MKC-06, MKC-06P and FR-02
A5049 Rev.2
EN
The voltage asymmetry causes the rise in motor temperature and a reduction of the
rated motor power.
Voltage asymmetry limit values can be adjusted between 5%-15% by the user or can
be disabled. Hysteresis is 30% of the adjusted asymmetry value.
Example: Given 3x380 V supply with 10% asymmetry,
Relay switches OFF at: 380-(10x400/100)=340 V
Relay switches ON at: 380-((10-(10x%30))x400/100)=353,2 V
Phase Sequence Fault Function Diagram
When the phase sequence is correct
(L1, L2, L3 in clockwise direction) the
output relay is activated; however, if
the sequence is changed by any
reason, the output relay switches OFF
immediately. Relay LED is OFF, Phase
Sequence error LED turns ON.
3-Lost Phase Fault
(MKC-05 / 05P / 06 / 06P):
If the value for any of the phases drop
d o w n   t h e   l o s t   p h a s e   l i m i t
value(Unx0.5), Phs.Seq. - Asm. LEDs
turn on simultaneously and the relay
breaks contact wthout delay.
4- Insufficient Supply Voltage (MKC-05 / 05P / 06 / 06P and FR-02 )
In devices which are supplied from a 3 phase capacitive source(MKC-05/06), the
supply voltage is the mean value of voltages from all three phases. If this mean value
(L3 phase for MKC-05P/06P devices) is less than half the supply voltage, the relay
gives an insufficient supply voltage warning(asm. and Phs. Seq. LEDs flash alternately)
and the relay breaks contact without delay.
MKC-05 and FR-02 with Neutral => (VL1+VL2+VL3)/3 < 115 VAC (P-N)
MKC-05P => VL3< 110 VAC (P-N)
MKC-06 without Neutral => (VL12+VL23+VL31)/3 < 200 VAC (P-P)
MKC-06P => VL31< 190 VAC (P-P)
ON
Asm.
Phs. Seq.
OUT
3
1
2
Phase
Failure
}
Phase Sequence
Fault
L1, L2, L3
L3, L2, L1
Precautions For Installation and Safe Use
Failure to follow those instructions will result in death or serious injury.
  Disconnect all power before working on equipment.
  When the device is connected to the network, do not remove the front panel.
  Do not try to clean the device with solvent or the like. Only clean the device
  with a dried cloth.
  Verify correct terminal connections before operation.
  Mount device to the panel.
  Electrical equipment should be serviced only by your compedent seller.
No responsibility is assured by the manufacturer or any of its subsidiaries
for any consequences arising out of the use of this material.
General
One of the common faults encountered in
industrial plants is the overheating and the
resulting damaging of the 3-phase motors
due to the phase failure. “Thermal-magnetic
relay” which is an essential element in motor
protection is generally too slow to assure
demurrage without tripping due to both its
PROTECTION FEATURES :
1- Voltage Unbalance (Can be Adjusted or Disabled) (MKC-05 / 05P / 06 / 06P)
Unbalanced voltage(asymmetry) may occur when;
    The mains are loaded with unbalanced distribution,
    One of the 3 phases of the motor has lost. In this case, some amount of voltage
which is produced by other phases will be induced on the lost phase. Amount of this
voltage depends on both the motor type and amount of load.
    Output relay is making contact when a phase has been lost or an unbalanced Phase-
Phase voltage value, which is occured for any reason, is smaller than the user defined
asymetrical value. If this unbalanced voltage value exceeds the adjusted asymetrical
value(5-15%); output relay will break contact and switch off the motor at the end
of adjusted time delay(0.1-20 sec.); relays LED on the front panel is turned off. Asymmetry
error LED is turned ON. If the fault disappears within the delay time, the output relay
will not break contact and will not switch off the motor.
    In applications; a proper asymetrical value should be adjusted considering the
induced voltage value in two-phase which are remained after the other one has
lost.
electromechanical structure and the use of high current setting range.MKC-05-05P,
MKC-06-06P  and FR-02 Motor Protection Relays which are designed to protect the
desired equipment against phase failure, asymmetry and phase sequence failure on
3 phase systems with or without neutral connection, are manufactured to serve the
following purposes.
Utilisation and Working Principle
By using the asymmetry adjustment knob(%asm.) on the front panel, the upper
asymmetry limit of the system which will be protected is determined. If the unbalance
on the system(asymmetry) exceeds the adjusted value, the device waits as long as
the Delay-OFF time(Delay) and if the unbalance is still over the adjusted value, the
relay of the device breaks contact(OUT LED turns off and Asm. LED turns on). If the
unbalance on the system(asymmetry) falls under the adjusted value, the device waits
as long as the Delay-ON time(Reset Delay) and if the unbalance is still under the
adjusted value, the relay of the device makes contact(OUT LED turns on and Asm.
LED turns off).
V
L3
VRef = 400 VAC
  (380 VAC MKC-06P)
V
L12
V
L31
L31
L12
V
L23
Without Neutral
With Neutral
VRef = 230 VAC
  (220 VAC MKC-05P)
Meanings of the Device LEDs
On Out
:Flashing
:LED OFF
:LED ON
Phs. Seq.
Asm.
PTC fault
Phase Fault Warning
Phase Sequence Fault Warning
Unsufficient Supply Warning
NC
C
NO
N
L1 L2 L3
1
2
3
Off
3
2
1
OUT
ON
Asm.
Phs. Seq.
%
Asm.
Reset
Delay
(s)
Delay
(s)
Relay Output
Supply / Measurement
 Inputs
Asymmetry Adjustment
Delay-ON Adjustment
Asymmetry Warning LED
Phase Sequence
Warning LED
Supply LED
Relay LED
Delay-OFF Adjustment
Voltage(s) is(are) within adjusted limits
Voltage(s) is(are) out of adjusted limits
Voltage(s) is(are) out of adjusted limits
(Delay time waiting)
3- PTC Protection (MKC-05P / 06P)
100k
10k
1k
100
10
20 40 60 80 100 120 140160 180 200
Temperature (
0
C)
R(
W
)
If motor coil temperature exceeds the
temperature limit of PTC, the motor is
disconnected immediately. The output relay
is opened and Relay LED turns off.
This feature is only available for MKC-05P
and MKC-06P. Resistance-Temperature
values for three PTC with different temperature
limit values (110 
o
C, 120 
o
C, 130 
o
C )
are shown on the figure on the right.
If you want to cancel PTC protection on a
device with PTC protection feature, the PTC
terminals on the device should be short-
circuited.
BREAK OF THE NEUTRAL CONNECTION FOR DEVICES WITH NEUTRAL
 (MKC-05/05P/FR-02):
In devices with neutral, Phase-Neutral measurements are taken. If the
neutral cable breaks, the neutral point of the system shifts because of
the asymmetrical phase loading. The device continues the take
measurements according to the shifted neutral system point. MKC-05P
is supplied from Neutral and L3 Phase. Break of neutral cable causes
the device to lose supply and the relay to open.
Connection Diagrams
C1
T1
Stop
T1
M
3 ~
Start
L1
L2
L3
N
C1
N
L1 L2 L3
FR-02
MKC-05
1 2 3
N
C1
T1
Stop
T1
M
3 ~
Start
L1
L2
L3
C1
N
L1 L2 L3
MKC-06
1 2 3
Dimensions (mm)
C1
T1
Stop
T1
M
3 ~
Start
L1
L2
L3
N
C1
N
L1 L2 L3
MKC-05P
1 2 3
PTC
PTC
N
C1
T1
Stop
T1
M
3 ~
Start
L1
L2
L3
C1
N
L1 L2 L3
MKC-06P
1 2 3
PTC
PTC
TYP PK 28
TECHNICAL PROPERTIES
: 48 ... 63 Hz. MKC-05 / 06, FR-02
: 50/60 Hz. MKC-05P / 06P
: 30 VA / 2 W (50 Hz.)
: True RMS
: 5%...15% (With/Without Neutral) Can be disabled.
: 30% of the adjusted asymmetry value
: 0.1 ... 20 sec.
: 0.1 ... 20 sec.
: ± 3%
: ± 0.5%
: ± 5% + 100 msec.
: ± 3%
: 1 Change-over(CO) Contact, 8A, 250V, 2000VA (Cosj=1)
: 10
5
: 10
7
: -5°C ... +55°C
: <%90 (without condensation)
: 4mm² (12AWG) 
stranded rigid cable
: 6mm² (10AWG) 
solid conductor cable
: 2x2.5mm² (
14AWG
solid conductor cable
: 0.5 Nm (4.5in.lbs)
Measurement and Supply Circuit
: 230V AC MKC-05 / 05P, FR-02
: 400V AC MKC-06 / 06P
: 150...300V AC MKC-05 / 05P, FR-02
: 270...510V AC MKC-06 / 06P
: Inside the panel vertically or on to the rail
: Plastic Compliant with UL 94 VO
: IP 20 (Terminals), IP 40 (Front Panel)
: Type PK 28
: 100 gr. Only MKC-05P / 06P 200gr
: 400 V
: Exceeding Voltage Category III,
  Pollution Degree 3
: 4 kV 1.2 / 50 uS
: 2 kV AC 50 Hz. 1  minute.
: >500 MOHM / 500 V DC
: Product Standard
: Immunity
: Emission
LVD
EMC
Supply Voltage (Un)
Supply Voltage Gap (
U
)
Supply Frequency
Power Consumption (max.)
Measurement Method
Settings
Asymmetry Adjustment Range(asm. %)
Hysteresis
Delay-Off(Delay)
Delay-On(Reset Delay)
Voltage Adjustment Accuracy
Repetition Accuracy(Voltage)
Accuracy of the Set Times
Repetition Accuracy(Time)
Output
Output Type
Electrical Life
Mechanical Life
Ambiant Conditions
Operating Temperature
Relative Humidity
Connection
Cable Cross-sections for Terminals
Screw-On Force
Body
Installation
Material Type
Protection Class
Dimensions
Weight
Isolation
Isolation Voltage (EN 60255-5)
Isolation Coordination
(EN 60255-5)
Instant Burst Voltage (EN 60255-5)
Dielectric Resistance (EN 60255-5)
Isolation Resistance (EN 60255-5)
Followed Standards
EN-60255-6
EN-61000-6-2
EN-61000-6-3, EN-61000-6-4
Directives/Regulations To Be Followed
73/23/EEC
89/336/EEC
2- Phase Sequence Protection
(MKC-05 / 05P / 06 / 06P and FR-02):
V
L1
V
’
L1
V
’
L2
V
L2
VRef
x 100
Asymmetry % =
VRef
x 100
Asymmetry % =
Max(PN) - Min(PN)
Max(PP) - Min(PP)