6.0 Electrical 
Connection 
 
ƒ  Move valve to mid-position by override nut.  This will allow sufficient time to stop actuator in case of  
improper hook-up 
ƒ  Identify means of removing power during hook-up 
ƒ  Be sure no erroneous remote control signals can be received causing actuator to energize 
ƒ  Electrically operate the valve in the open direction.  If the valve closes, actuator must be stopped and 
checked for improper field wiring 
ƒ 
Set all field conduit entries in accordance with National Electric Code Requirements
 
 
 
7.0      Limit Switch Setting Instructions 
 
•  Operate the actuator manually to closed 
position 
•  Using a hex wrench, loosen the cam adjustment 
screw in the CLS limit switch cam 
•  Rotate the CLS cam towards limit switch lever 
until the switch ‘clicks’ 
•  Tighten set screw with hex wrench 
•  Operated the actuator manually to open position 
•  Using a hex wrench, loosen the cam adjustment 
screw in the OLS limit switch cam 
•  Rotate the OLS can towards  limit switch lever 
until the switch ‘clicks’ 
•  Tighten set screw with hex wrench 
•  Repeat for AOLS and ACLS 
 
 
8.0 Lubrication 
 
The HQ series actuators are totally enclosed units with a permanently lubricated gear trains (Moly EP 
Grease). Once installed lubrication should not be required.   However, periodic preventative maintenance 
will extend the operating life of the actuator.  
 
 
9.0 MDPI 
Settings
 
 
ƒ  Manually rotate actuator to fully closed position 
ƒ  Remove actuator cover 
ƒ  Loosen indicator screw 
ƒ  Adjust indicator to correct orientation 
ƒ  Tighten indicator screw 
ƒ Replace 
cover 
ƒ  Check  indicator alignment