Westinghouse CONTRACTOR SERIES 10KPRO FULLY FEATURED Owner's Manual

Page of 106
26 
OPERATION
Transfer Switch Cord
The transfer switch cord, 10KPRO Part No. 210051 and 
8KPRO Part No. 210075, is an optional accessory for 
the portable generator. It is used to connect the 50-amp 
outlet on the 10KPRO and the 30-amp outlet on the 
8KPRO of the generator to the transfer switch. If your 
transfer switch does not come with a transfer switch 
cord, order the cord from Westpro Power.
Figure 17 – Transfer Switch Cord, 10KPRO
Figure 18 – Transfer Switch Cord, 8KPRO
TRANSFER SWITCH 
CONNECTIONS
The Westinghouse generator is wired with the neutral 
bonded to ground. If you are connecting your generator 
to a transfer switch, the electrician must first determine 
what type transfer switch is being used. Transfer 
switches for this equipment are either two-pole or three-
pole types.
A two-pole transfer switch will not switch the neutral 
from the generator to the service panel. That means 
the generator will be grounded to the service panel. To 
use the generator with two-pole transfer switches, the 
electrician will need to change the neutral from bonded 
to floating. 
Remove the ground screw from the wires (see Figure 
19)
. Wrap the terminal end of the green wire with 
electrical tape so it is insulated. Tape the green wire to 
the yellow/green wire so it cannot contact any moving 
parts. Connect the yellow/green wire back to ground 
using the ground screw.
3
2
1
Figure 19 – Bonding Wire
1 -   Ground Screw
2 -  Green Wire
3 -   Yellow/Green 
Wire