Westinghouse WGR050LP076 Installation Instruction

Page of 60
39 
 
 
                                                                                  WHL-001 REV. 12.17.14 
 
The gas supply shall have a maximum inlet pressure of less than 14" water 
column (350 mm), ½ pound pressure (3.5 kPa), and a minimum of 3.5" water 
column. The entire piping system, gas meter and regulator must be sized 
properly to prevent pressure drop greater than 0.5" WC as stated in the 
National Fuel Gas Code. This information is listed on the rating plate. 
 
It is very important that you are connected to the type of gas as noted on the 
rating plate: "LP" for liquefied petroleum, propane gas, or "Nat" for natural or 
city gas. All gas connections must be approved by the local gas supplier or 
utility, in addition to the governing authority, prior to turning the gas supply 
on. 
 
Do not remove the adaptor in 
! It is mandatory that this fitting is used 
for connection to a field fabricated drip leg per the National Fuel Gas Code. 
You must ensure that the entire gas line to the connection at the water heater 
is no 
smaller than ½”. 
 
Once all inspections have been performed, the piping must be leak tested. If 
the leak test requirement is a higher test pressure than the maximum gas 
inlet pressure, you must isolate the heater from the gas line to continue leak 
testing. To do this, you must turn off the factory and field-installed gas cocks. 
This will minimize the possibility of damaging the gas valve. Failure to do so 
may damage the gas valve. In the event the gas valve is exposed to a 
pressure greater than ½ PSI, 14" water column, the gas valve must be replaced. Never use an open flame (match, lighter, etc.) to 
check gas connections. 
 
 
UL recognized fuel gas detectors are recommended in all enclosed propane and natural gas applications where there is a potential for 
an explosive mixture of fuel gas to accumulate. The installation of these detectors should be made in accordance with the detector 
manufacturer’s recommendations, and/or local laws. Failure to install fuel gas detectors in these applications could result in fire, 
explosion, property damage, severe personal injury, or death. 
A. GAS PIPING 
Run the gas supply line in accordance with all applicable codes. Locate and install manual shutoff valves in accordance with local and 
state requirements. 
 
 
Support gas supply piping with hangers, not by the heater or its accessories. The heater gas valve and blower will not support the 
weight of the piping. Make sure the gas piping is protected from physical damage and freezing, where required. Failure to follow these 
instructions could result in gas leakage, and result in fire, explosion, property damage, severe personal injury, or death. 
 
 
Do not use Teflon tape on gas line pipe thread. Use a pipe compound rated for use with natural and propane gases. Apply sparingly on 
male pipe ends, leaving the two end threads bare. Failure to follow these instructions could result in gas leakage, and result in fire, 
explosion, property damage, severe personal injury, or death. 
B. GAS TABLE 
Refer to the table below to size the supply piping to minimize pressure drop between meter or regulator and unit. 
 
Maximum capacity of pipe in cubic feet of gas per hour for gas pressures of .5 psi or less and a pressure drop of .3 inch water column. 
 
Nominal Iron 
Pipe Size (In.) 
Internal 
Dia. (In.) 
Length of Pipe (Feet) 
BTU’s 
Per Hour 
1,000 
 
10 
20 
30 
40 
50 
60 
70 
80 
90 
100 
125 
150 
175 
200 
½ 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
¾ 
.824 
278 
190 
152 
130 
115 
105 
96 
90 
84 
79 
72 
64 
59 
55 
1.049 
520 
350 
285 
245 
215 
195 
180 
170 
160 
150 
130 
120 
110 
100 
1 ¼ 
1.380 
1,050 
730 
590 
500 
440 
400 
370 
350 
320 
305 
275 
250 
225 
210 
Table 9 
– Source – ANSI Z223.1 
Figure 20 
–Gas Connection