Westinghouse WGR050LP076 Installation Instruction

Page of 60
41 
 
 
                                                                                  WHL-001 REV. 12.17.14 
PART 8 – CONTROLS 
A. CONTROL AND DISPLAY OVERVIEW 
 
Detailed Description of Button 
Functions 
 
1. Setting Adjust Down
 
 
2. Setting Adjust Up 
 
3. Decreases the User Setpoint 
 
4. Increases the User Setpoint 
 
5. ECO Mode 
 
6. RESET 
 
7. OFF / Mode Enable 
 
 
Detailed Description of Control Functions
 
MODES OF OPERATION 
MODE 
SCREENSHOT 
DESCRIPTION 
RANGE (DEFAULT) 
Off Mode 
 
The water heater will ignore heat demands while in Off Mode. 
 
To put the water heater into Off Mode, press 
Off / On (Off) 
Stand-By 
Mode 
 
In Stand-By Mode, the fan is off, the gas valve is closed, and 
the water inlet shut-off valve is opened. 
 
The water heater goes into Stand-By Mode when it is powered 
but not firing. 
On Winter / On 
Summer / Off (Off) 
User 
Setpoint 
 
The User Setpoint is used to set the temperature for the water 
heater. 
Press either 
 or 
 once to change the User Setpoint. 
The normal operation screen will clear and be replaced by a 
flashing number. This is the User Setpoint. 
Press 
 to decrease or 
 to increase the setpoint in 
increments of two degrees. After choosing the setpoint, wait 
five seconds. The screen will return to normal operation and 
the setpoint will be stored. 
70 
– 160 (120) 
Outdoor 
Reset Curve 
 
Enabling Outdoor Reset Curve allows the user to set 
additional parameters to increase water heater efficiency. 
 
An Outdoor Sensor is required to set Outdoor Reset Curve. 
 
See Advanced Control Functions to set the Outdoor Reset 
Curve. 
0 = Enabled, 1 = 
Disabled (0) 
Figure 22 
– Control Detail