Siemens Welding System ST PCS 7 User Manual

Page of 344
Communication
Industrial Ethernet
OSM/ESM/OMC Industrial Ethernet switches
9/21
Siemens ST PCS 7 · November 2007
9
Overview
The Industrial Ethernet OSM and ESM switches are used to con-
struct Industrial Ethernet networks at the control level:
• The modules are interconnected (backbone) at 100 Mbit/s 
over
- Glass fiber-optic cables (FO) for OSM 
- Twisted pair cables for ESM
• Connection of data terminals or network segments depending 
on the OSM/ESM type through 
- 2 to 8 twisted pair ports 10/100BaseTX in RJ45 or 9-pole 
Sub-D design for 10/100 Mbit/s
- 3 or 8 FO ports 100BaseFX with BFOC interface (ST socket) 
for 100 Mbit/s
• Integral redundancy manager supports high-speed media re-
dundancy also for large networks
• Very easy network configuration and extension without com-
plex configuration rules or parameterization
Application
Industrial Ethernet OSM and ESM
The Industrial Ethernet OSM (Optical Switch Module) and ESM 
(Electrical Switch Module) are used in the construction of 
switched networks with data transmission rates of 100 Mbit/s in 
the control level range, in which strict demands are placed on 
network availability and comprehensive diagnostics are re-
quired.
In existing networks, load decoupling and thus increased net-
work performance can be achieved by creating segments (di-
viding a network into subnetworks/segments) and connecting 
these segments to an OSM/ESM.
The redundancy manager integrated into OSM/ESM allows In-
dustrial Ethernet rings to be constructed in switching technology 
with high-speed switching over of the communication path on 
failure of a switch or interruption in the transmission path (recon-
figuration time max. 0.3 seconds). 
The transmission rate in the ring is 100 Mbit/s; for each ring, up 
to 50 Industrial Ethernet OSMs (optical ring) or ESMs (electrical 
ring) can be used. Apart from the 2 ring ports, OSM/ESM has 
other ports (with either RJ45, ITP or BFOC interfaces) to which 
data terminals or network segments can be connected.
Selection support for the various product versions of OSM is pro-
vided by the table under "Technical specifications".
Industrial Ethernet media converter
Industrial Ethernet nodes with RJ45 TP interface can be con-
nected via an Industrial Ethernet media converter to one of the 
8 optical ports of an OSM BC08. The two types of media con-
verter SCALANCE X101-1 or X101-1LD convert the electric 
twisted-pair interface, port type 10/100BaseTX (10/100 Mbit/s, 
RJ45 socket) as follows:
• X101-1: into an optical interface for multimode glass FOC
• X101-1LD: into an optical interface for singlemode glass FOC
The port type of the optical interface is 100BaseFX in each case 
(100 Mbit/s; 2 x BFOC socket).
Notes
:
Just like the OMC TP11 media converter, the SCALANCE X101-1 does 
not support diagnostics per SNMP protocol.
For further information on the Industrial Ethernet media converter, see 
Catalog IK PI, Section "Active network components - Industrial Ethernet 
media converter".
Technical specifications
Selection support for product versions of OSM and ESM
1)
TP cable preferably inside a control cabinet
2)
For cross-building connection of Fast Ethernet networks with OSM
3)
For design of an optical network, where TP cables are preferably only used 
inside control cabinets
4)
Connects a station with RJ45-TP interface to one of the 8 optical ports of 
an OSM BC08
5)
Inside buildings
6)
Inside switchrooms
Type and 
number of ports
Preferentially 
for use
RJ
45
 (T
P
)
Su
b-D
 (ITP
)
Mul
ti-mode FO
Si
ng
le
-mod
e F
O
With 
high 
EMC 
loading
For 
plant 
bus
For ter-
minal 
bus 
(OS-
LAN)
OSM TP22
2
2
n
1)
n
n
OSM ITP62 
(Standard)
6
2
n
n
n
OSM TP62
6
2
n
n
OSM ITP62-LD
6
2
n
n
n
OSM ITP53
5
3
n
n
2)
n
2)
OSM BC08
–-
8
n
3)
n
3)
n
3)
SCALANCE 
X101-1
1
–-
1
n
4)
n
4)
n
4)
SCALANCE 
X101-1LD
1
–-
–-
1
n
4)
n
4)
n
4)
ESM ITP80
8
n
n
5)
n
ESM TP40
4
n
6)
n
ESM TP80
8
n
6)
n
© Siemens AG 2007