Siemens Welding System ST PCS 7 User Manual

Page of 344
Communication
PROFIBUS DP
Y-Link
9/42
Siemens ST PCS 7 · November 2007
9
Overview
The Y-link is a bus coupler for transition from a redundant 
PROFIBUS DP master system to a single-channel 
PROFIBUS DP master system. It can be used for connecting de-
vices with only one PROFIBUS DP interface to the redundant 
PROFIBUS DP master system AS 414H/ AS 417H.
Design
The Y-link comprises:
• Two IM 153-2 High Feature interface modules for extended 
temperature range
• One Y-coupler incl. RS 485 repeater
• One IM 157 (IM/IM) bus module for two IM 153-2 High Feature 
modules, for extended temperature range
• One BM Y-coupler bus module
Evaluation of the Y-Link diagnostics (and hence indirectly of the 
connected DP standard slaves) is supported by driver blocks.
It is recommendable to have a redundant -24 V DC supply for 
the Y-Link, e.g. with two PS 307/PS 305 load power supplies.
B) Subject to export regulations: AL: N, ECCN: EAR99H
Fault-tolerant 
automation system
Connection of non-redundant 
PROFIBUS DP devices to 
redundant PROFIBUS DP 
Y-Link 
redundant PROFIBUS DP
 
Selection and Ordering Data
Order No.
Y-Link
For connection of devices with 
only one PROFIBUS DP interface 
to a fault-tolerant automation sys-
tem, comprising:
• 2 IM 153-2 High Feature inter-
face modules
• 1 Y-coupler
• 1 BM IM 157 bus module (IM/IM)
• 1 BM Y-coupler bus module
6ES7 197-1LA11-0XA0
B)
PS 307 load power supply
Including connection assembly; 
120/230 V AC; 24 V DC
• 2 A; 50 mm wide
6ES7 307-1BA00-0AA0
• 5 A; 80 mm wide
6ES7 307-1EA00-0AA0
• 5 A, extended temperature 
range; 80 mm wide
6ES7 307-1EA80-0AA0
• 10 A, 200 mm wide
6ES7 307-1KA01-0AA0
PS 305 load power supply
24/48/60/110 V DC; 24 V DC
• 2 A, extended temperature 
range; 80 mm wide
6ES7 305-1BA80-0AA0
© Siemens AG 2007