Communication
PROFIBUS PA
Active field distributor AFD
and active field splitter AFS
9/49
Siemens ST PCS 7 · November 2007
9
Overview
 
Active field distributor AFD 
An active field distributor (AFD) can integrate up to 
4 PROFIBUS PA field devices via short-circuit proof spur line 
connections into a PROFIBUS PA ring with automatic bus termi-
nation. The PROFIBUS PA ring is connected to two FDC 157-0 
DP/PA couplers of a DP/PA router. Up to 8 AFDs and up to 
31 PROFIBUS PA devices can be configured per ring. The num-
ber of PROFIBUS PA devices is additionally limited by the max. 
current consumption of 1 A for all devices.
An AFD can be replaced during operation. The function of the 
PROFIBUS PA devices on the other AFDs is not influenced by 
this.
Active field splitter AFS
The active field splitter (AFS) connects a PROFIBUS PA line with 
two redundant FDC 157-0 DP/PA couplers of a DP/PA router. The 
AFS switches the PROFIBUS PA line to the active one of the two 
redundant couplers.
Up to 31 PROFIBUS PA devices can be connected on the 
PROFIBUS PA line. This number is additionally limited by the 
max. current consumption of 1 A for all devices.
Technical specifications
 
 
B) Subject to export regulations: AL: N, ECCN: EAR99H
Active field distributor AFD and active field splitter AFS
Active field distributor AFD
 
Connection of PROFIBUS PA field 
devices
• Max. 4 per AFD
• Max. 31 per ring
• Operating environment up to 
zone 2 or 22
• Max. current consumption of all 
devices 1 A
Current Imax. per spur line X1 to X4
60 mA
Power supply
16 V DC (16 ... 32 V)
Current consumption
Approx. 20 mA
Power loss
Approx. 600 mW
Output voltage for PA section
31 V 
±
1 V  DC
Voltage failure bridging
5 ms
Output current for PA section (for 
dimensioning of device configura-
tion)
1 A
Diagnostic displays
Status PA main line PA1, PA2 
(green)
Fault PA main line PA1, PA2 (red)
Status/fault PA spur line X1 to X4 
(green)
Permissible operating temperature
-25 ... +70 °C
Dimensions (W x H x D) in mm
120 x 57 x 80
Weight
Approx. 700 g
Active field splitter AFS
 
Connection of PROFIBUS PA field 
devices
• Max. 31 per line
• Operating environment up to 
zone 2 or 22
• Max. current consumption of all 
devices 1 A
Power supply
16 V DC (16 ... 32 V)
Current consumption
Approx. 20 mA
Power loss
Approx. 600 mW
Output voltage for PA section
31 V 
±
1 V  DC
Voltage failure bridging
5 ms
Output current for PA section (for 
dimensioning of device configura-
tion)
1 A
Diagnostic displays
Status PA main line PA1, PA2 
(green)
Fault PA main line PA1, PA2 (red)
Permissible operating temperature
-25 ... +70 °C
Dimensions (W x H x D) in mm
120 x 57 x 80
Weight
Approx. 700 g
Selection and Ordering Data
Order No.
Active field distributor AFD
with 4 short-circuit-proof spur line 
connections for integration of field 
devices
6ES7 157-0AF81-0XA0
B)
Active field splitter AFS
for connecting a PROFIBUS PA 
line to 2 redundant FDC 157-0 
DP/PA couplers; automatic 
switchover to the active coupler
6ES7 157-0AF82-0XA0
B)
Profile rail adapter 
for an active field distributor AFD 
or active field splitter AFS, 
optional
6ES7 157-0AF83-0XA0
Active field distributor AFD and active field splitter AFS
© Siemens AG 2007