Overview
The IM 153-2 High Feature interface module (electrical 
PROFIBUS DP transmission) or IM 153-2 FO High Feature inter-
face module (optical PROFIBUS DP transmission) is required to 
connect the ET 200M remote I/O station to the PROFIBUS DP 
fieldbus. Depending on the fieldbus configuration (single/redun-
dant), the ET 200M remote I/O station can be connected via one 
single or two redundant interface modules.
The IM 153-2 High Feature supports the following functions:
7
HART configuring of intelligent field devices
7
Configuration of ET 200M I/Os in RUN mode of the automation 
system
7
Connection to redundant AS 412H / AS 414H / AS 417H auto-
mation systems
7
Use of ET 200M function modules (controller and counter 
modules)
7
Operation of up to 12 I/O modules per remote I/O station
7
Time stamping (SOE) with the safety-related SM 326F digital 
input module (F-DI24)
7
Transmission of additional values with HART secondary vari-
ables of the HART SM 331 and SM 332 analog modules (up to 
4 per channel or up to 8 per module)
On the other hand, the fiber-optic (FO) version IM 153-2 FO High 
Feature provides the following functions:
7
HART configuring of intelligent field devices
7
Configuration of ET 200M I/Os in RUN mode of the automation 
system
7
Connection to redundant AS 412H, AS 414H  and AS 417H 
automation systems
7
Use of ET 200M function modules (controller and counter 
modules)
7
Operation of up to 8 I/O modules per remote I/O station
Notes:
In order to use the hot swapping function, it is necessary to use the active 
bus modules and the DIN rail for hot swapping (refer to page 11/12).
When using the IM 153-2 FO, additional plastic FOCs and an assembly 
set for Simplex connectors are required (refer to page 9/40).
B) Subject to export regulations: AL: N, ECCN: EAR99H
Selection and Ordering Data
Order No.
IM 153-2 High Feature
Slave interface module for con-
nection of an ET 200M to 
PROFIBUS DP, with time stamp 
(accuracy 1 ms), support of 
HART functionality, F modules, 
FM modules, "Configuration in 
RUN" function; also for use in 
redundant systems
6ES7 153-2BA02-0XB0
B)
IM 153-2 FO High Feature
Slave interface module for con-
nection of an ET 200M to optical 
PROFIBUS DP; support of HART 
functionality, F modules, FM mod-
ules, "Configuration in RUN" func-
tion; also for use in redundant 
systems
6ES7 153-2BB00-0XB0
B)