Siemens Welding System ST PCS 7 User Manual

Page of 344
Process I/O
ET 200M distributed I/O
Ex modules [EEi xb]
11/22
Siemens ST PCS 7 · November 2007
11
Overview
The following analog and digital I/O modules are suitable for use 
in hazardous plants. They separate the non-intrinsically safe 
electrical circuits of the automation system and the intrinsically 
safe electrical circuits of the process. Sensors and actuators 
suitable for placing in zone 1 or 21 and 2 or 22 hazardous areas 
as well as intrinsically safe equipment compliant with DIN 50020 
and [EEx ib] IIC can be operated on these modules.
All Ex modules come with diagnostics capability (channel and 
module diagnostics).
Ex modules identified by "redundant design possible" 
(6ES7 321-7RD00-0AB0, 6ES7 322-5SD00-0AB0, 6ES7 331-
7RD00-0AB0, 6ES7 332-5RD00-0AB0) can also be configured 
redundant when used in non-hazardous plants.
For additional Ex modules, refer to page 11/23.
Selection and Ordering Data
Order No.
Ex digital input module
 
4 NAMUR inputs in 4 channel 
groups
Redundant design possible 
(module redundancy)
• Voltage supply to sensors 8.2 V
• Individually floating channels
• Wire break and short-circuit 
monitoring (directly at the con-
tact for contacts with external 
resistor circuit)
• Diagnostics inside module 
• Front connector required: 
20-contact
6ES7 321-7RD00-0AB0
Ex digital output module
 
4 outputs, 24 V DC / 10 mA in 
4 channel groups
Redundant design possible 
(module redundancy)
• Individually floating channels
• Wire break monitoring
• Short-circuit monitoring
• Diagnostics inside module 
• Front connector required: 
20-contact
6ES7 322-5SD00-0AB0
4 outputs, 15 V DC / 20 mA in 
4 channel groups
• Individually floating channels
• Wire break monitoring
• Short-circuit monitoring
• Diagnostics inside module 
• Front connector required: 
20-contact
6ES7 322-5RD00-0AB0
Ex analog input module
 
4 inputs, 0/4 to 20 mA in 
4 channel groups
Redundant design possible 
(module redundancy)
• Individually floating channels
• Resolution 15 bit + sign
• Connection of 2-wire or 4-wire 
transmitters possible
• Wire break monitoring
• Measurement range monitoring
• Short-circuit-proof
• Diagnostics inside module 
• Front connector required: 
20-contact
6ES7 331-7RD00-0AB0
8 inputs in 4 channel groups
• Resolution 15 bit + sign
• Thermocouples type T, U, E, J, 
L, K, N, R, S, B (8 channels)
Internal compensation; external 
compensation with Pt100 
(2 channels), compensating box 
or 0/50 °C cold junction
• Resistance thermometer Pt100, 
Pt200, Ni100 (4 channels; 2-wire 
or 4-wire, 3-wire Pt100 on 
request)
• Wire break monitoring
• Diagnostics inside module 
• Front connector required: 
20-contact
Note
:
A special front connector for the 
Ex analog input module 6ES7 
331-7SF00-0AB0 enables greater 
accuracy when taking thermo-
couple temperature measure-
ments in "internal compensation" 
mode (see page 11/12).
6ES7 331-7SF00-0AB0
Ex analog output module
 
4 outputs, 0/4 to 20 mA in 
4 channel groups
Redundant design possible 
(module redundancy)
• Individually floating channels
• Resolution 15 bit
• For 2-wire transmitters
• Wire break monitoring
• Diagnostics inside module 
• Front connector required: 
20-contact
6ES7 332-5RD00-0AB0
Selection and Ordering Data
Order No.
© Siemens AG 2007