Siemens Welding System ST PCS 7 User Manual

Page of 344
Process I/O
ET 200M distributed I/O
F modules
11/25
Siemens ST PCS 7 · November 2007
11
Overview
The safety functions of the AS 414F/FH and AS 417F/FH automa-
tion systems are matched to the safety-related I/O modules 
(F-modules) of the ET 200M distributed I/O system. The F-signal 
modules (DI/DO/AI) in the ET 200M remote I/O stations are able 
to guarantee plant safety even in the event of a CPU failure. They 
are of redundant design, and can diagnose both internal and ex-
ternal faults. They carry out self-tests for this purpose, e.g. for 
short-circuit or wire breakage, and automatically monitor the dis-
crepancy time defined in the parameter settings. They comply 
with the requirements up to SIL 3 (IEC 61508) or AK 6 
(VDE 0801). 
The input modules operate internally with single-channel evalu-
ation (SIL 2 sensors), 2-out-of-2 evaluation (SIL 3 sensors) or 
2-out-of-3 channel evaluation (only F-AI module). A safety re-
sponse is triggered immediately there are any differences. The 
type of evaluation influences the number of usable inputs (chan-
nels). For example, only half of the existing inputs are available 
in the case of 2-out-of-2 channel evaluation. 
The digital output modules enable safe disconnection through a 
second disconnect path in the event of a faulty output.
Selection and Ordering Data
Order No.
SM 326F failsafe digital input module
 
for floating contacts
 
24 inputs, 24 V DC
Electrically isolated in groups 
of 12
Redundant design possible 
(module redundancy)
• 4 short-circuit-proof sensor 
power supplies, each for 
6 channels, isolated in groups 
of 3
• External sensor power supply 
possible
• SIL 2: single-channel evaluation, 
24 channels
• SIL 3: 2-out-of-2 evaluation on 
the module, 12 channels 
(adjustable discrepancy time)
• Short-circuit monitoring to L+
• Discrepancy monitoring
• Supports time stamping (SOE)
• Diagnostics inside module
• PROFIsafe telegram
• Front connector required: 
40-contact
6ES7 326-1BK01-0AB0
8 inputs, NAMUR [EEx ib]
Isolated by channel
Redundant design possible 
(module redundancy)
• 8 short-circuit-resistant sensor 
power supplies, each for 
1 channel, mutually isolated
• SIL 2: single-channel evaluation, 
8 channels
• SIL 3: 2-out-of-2 evaluation on 
the module, 4 channels 
(adjustable discrepancy time)
• Wire break and short-circuit 
monitoring (for contacts with 
external resistor circuit)
• Discrepancy monitoring
• Diagnostics inside module
• PROFIsafe telegram
• Front connector required: 
40-contact
6ES7 326-1RF00-0AB0
© Siemens AG 2007