Process I/O
ET 200iSP distributed I/O
RS 485-IS coupler
11/37
Siemens ST PCS 7 · November 2007
11
Overview
Tasks of the RS 485-iS coupler
• Conversion of the electrical PROFIBUS DP RS 485 transmis-
sion technology into the intrinsically-safe RS 485-iS transmis-
sion technology with a transmission rate of 1.5 Mbit/s
• Required to connect intrinsically-safe PROFIBUS DP stations, 
e.g. ET 200iSP, ET 200iS or devices from other vendors with 
Ex i DP connection
• Functionality as a safety barrier
• Additional use as a repeater in the hazardous area
• Passive bus station (no configuration necessary)
• Certified according to ATEX 100a
Design
• The RS 485-iS coupler is an open unit; assembly is only per-
missible in housings, cabinets or rooms for electrical equip-
ment.
• The RS 485-iS coupler is approved for use in hazardous areas 
of zone 2.
It must be fitted in a housing which at least corresponds to the 
IP54 degree of protection. A manufacturer’s declaration for 
zone 2 (according to EN 50021) is required for the housing 
and the necessary cable glands.
• The RS 485-iS coupler can be used in a horizontal or vertical 
position.
• Installation is on a SIMATIC S7-300 rail.
• Diagnostics LEDs on the front panel signal the operating sta-
tus.
Connection to PROFIBUS DP
• Connection to standard PROFIBUS DP via standard Sub-D 
socket (at the bottom on the RS 485-iS coupler, behind the 
right front door).
Integral bus connection for PROFIBUS DP with RS 485-iS 
transmission technology
• Connection of PROFIBUS DP with RS 485-iS transmission 
technology via screw terminals (at the top of the RS 485-iS 
coupler, behind the right front door)
• The last bus station on the intrinsically-safe PROFIBUS DP 
segment (not further RS 485-iS couplers) must be terminated 
by a selectable resistance using the connector, Order No. 
6ES7 972-0DA60-0XA0.
B) Subject to export regulations: AL: N, ECCN: EAR99H
Selection and Ordering Data
Order No.
RS 485-IS coupler
Isolating transformer for connec-
tion of PROFIBUS DP segments 
with RS 485 and RS 485-iS trans-
mission technologies
6ES7 972-0AC80-0XA0
Accessories
 
PROFIBUS connector with 
selectable terminating resistor
For connection of IM 152 to 
PROFIBUS DP with RS 485-iS 
transmission technology
6ES7 972-0DA60-0XA0
B)
S7-300 rails
Lengths:
• 160  mm
6ES7 390-1AB60-0AA0
• 482  mm
6ES7 390-1AE80-0AA0
• 530  mm
6ES7 390-1AF30-0AA0
• 830  mm
6ES7 390-1AJ30-0AA0
• 2000 mm
6ES7 390-1BC00-0AA0
PROFIBUS Fast Connect bus 
cable
Standard type with special design 
for fast mounting, 2-core, 
shielded, cut-to-length; max. 
delivery unit 1000 m, minimum 
ordering quantity 20 m
6XV1 830-0EH10