Siemens Welding System ST PCS 7 User Manual

Page of 344
Operator system
Redundant operator systems
OS redundancy
5/16
Siemens ST PCS 7 · November 2007
5
Overview
OS redundancy shown in a client/server architecture with high availability
OS single stations and OS servers can have a redundant design 
if necessary:
• A SIMATIC PCS 7 Single Station Redundancy programming 
package is required to design redundant OS single stations. 
This contains: 
- OS Software Single Station
- Software WinCC/Redundancy (in each case for two 
OS single stations)
- RS 232 cable connector for optimization of internal commu-
nication between the two OS single stations.
• A SIMATIC PCS 7 Server Redundancy programming package 
is required to design redundant OS servers. This contains: 
- OS Software Server 
- Software WinCC/Redundancy (in each case for two 
OS servers) 
- RS 232 cable connector for optimization of internal server-
server communication.
A separate Ethernet connection can be used instead of the serial 
RS 232 connection for optimization of internal communication 
between the two redundant stations (OS single 
stations/OS servers). This is an alternative e.g. with larger dis-
tances between the stations or if the COM interface is required 
elsewhere. 
An optical or electrical connection can be used depending on 
the environmental conditions and the distance between the re-
dundant stations, e.g. up to 100 m per crossover network cable 
with RJ45 connectors. For further information, refer to the Man-
ual "SIMATIC PCS 7 V7.0 fault-tolerant process control systems"; 
for appropriate cable material and further accessories, refer to 
Catalog IK PI (Industrial Communication). 
What further components are required depends on the plant ar-
chitecture. The design of the plant bus and terminal bus 
(OS-LAN) is of particular importance, as well as the type and 
number of subordinate automation systems. The maximum re-
quirements are determined by the redundant configuration 
shown in the figure with a fault-tolerant automation system and 
two redundant rings each for the plant bus and terminal bus. 
Design
The following table provides an overview of which components 
are required for a redundant OS single station or OS pair of serv-
ers depending on certain criteria:
AS 412H/
AS 414H/
AS 417H
Client Client 
OS-LAN (Ethernet), ring 1 
OS-LAN (Ethernet), ring 2 
Redundant servers 
Redundant Industrial Ethernet
plant bus (double ring) 
Up to 8 AS per single 
station/pair of servers
9 to 64 AS per single 
station/pair of servers
Min. 1 fault-tolerant 
AS
SIMATIC PCS 7 Indus-
trial Workstation, single 
station or server ver-
sion, alternatives
Incl. Ethernet network card 10/100/1000 Mbit/s 
and BCE
2
--
--
Incl. CP 1613 and S7-1613 software
2 (alternative to BCE)
2
2
SIMATIC PCS 7 Single Station/Server Redundancy V7.0 (including RS 
232 connecting cable)
1
1
1
S7-REDCONNECT Upgrade
--
--
2
Connection to redun-
dant plant bus 
(2 rings), alternatives
BCE
Desktop adapter network 
card
2
--
--
CP 1613
CP 1613 communications 
processor
2 (alternative to BCE)
2
2
S7-1613 software
2 (alternative to BCE)
2
--
S7-REDCONNECT software
--
--
2
Connection to redun-
dant terminal bus 
(2 rings)
SIMATIC PCS 7 Redundant Terminalbus 
Adapter Package
2
2
2
© Siemens AG 2007