Siemens FC700A User Manual

Page of 70
Auxiliary power supply 
26 
Siemens Building Technologies
 
 007836_a_en_--.doc
Fire & Security Products 
 
03.2004
 
 
11 
Auxiliary power supply 
11.1 Configuration 
 
31
51
23
27
37
47
57
46
56
A
28
38
48
58
AX1210
AX1201
or
Mains
terminals
AX1210
AX1201
or
View A
E3C01
1
B2
F
020
Z3
I47
0
H38G310
Module chassis
view 'Modules'
Cabinet front view
absolutely essential
B2F020
Converter 115/230VAC
-> 29.6VDC/6A
E3C011
Battery charging module
AX1201 / AX1210
Batteries
Z3I470
Cable set, terminal strip
with card holder
 
11.2 Block 
diagram 
 
* TF = Temperature sensor for battery temperature monitoring
Mains
Basic emergency
power supply
Extension
B2F020
TF*
TF*
Batteries
AX12..
Batteries
AX12..
Monitoring via HW monitoring path
FC700A
Mains
B2F020
E3C011
E3C011
Battery charging unit
H38G310
Cascading
 
 
Details see document 007831, chapter 'Cascading principle' 
To activate the supervision path of the E3C011, the device "Fu supply ext. supply 
supervision" must be created in the tool SWE700A. 
11.3 Modules 
 
 
Component Order-No.  Description 
Notes 
H38G310 
484930 
Housing set 
Door without cut-out 
B2F020 
470588 
Converter 115/230VAC -> 29,6VDC 6A 
 
E3C011 505479  Battery 
charging 
unit 
 
Z3I470 
484341 
Cable set with card holder 
 
AX1201 
225487 
Battery 12V / 27Ah 
Capacity based battery make 'ALARMCOM' (FIAMM) 
AX1210 
475570 
Battery 12V / 15Ah