12.5  Connection lines between control unit and external operating 
units 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
When planning a system the following condition must be complied with: 
 
At least one operating unit must comply with standard EN54, i.e. it must be 
equipped with emergency operation and emergency power supply. 
EN54 requirements: 
 
Communication as loop line -> design C-Bus as a loop line 
 
Operating units also with emergency operation -> 3 additional wires 
 
Second de-coupled 24V supply -> 3 additional wires or autonomous power 
 supply 
The number of wires in the connection cable depends on the application and the 
distances between the stations: 
 
Application C-Bus 
24V 
supply 
Emergency power 
supply 
Emergency opera-
tion circuit 
Number of wires 
24V supply from 
control unit 
EN54 complied with 
✔ 
(2 wires) 
✔ 
(3 wires) 
✔ 
(3 wires) 
✔ 
(3 wires) 
11 
24V supply from 
control unit without 
emergency operation 
and emergency 
power supply 
✔ 
(2 wires) 
✔ 
(3 wires) 
  5 
Note: 
– 
Emergency operation circuit required including between CPUs or for a sepa-
rately connected Gateway 
– 
Emergency operation circuit and emergency supply are not designed as a loop 
line 
– 
Emergency supply via separate cable or C-Bus feedback 
12.6  Power supply (24V) 
 
 
Operating unit B3Q700 is designed for the voltage range 18...45VDC 
 
The maximum current at 24V is 400mA 
 
Max. Length of line (approximate): 
– 
For cables ø 0.8mm -> 180m 
– 
For cable cross-section 1mm
2
 -> 360m 
 
The current consumption for the options (parallel indicator panel, LON-module) 
must be taken into account separately 
Control unit FC700A 
Options 
Control terminal FT700A
2…11 
leads 
Loop C-Bus 
max. 1000m per loop with 0,6mm G51 (incl. return line) 
max. 1400m per loop with 
0,8mm G51 (incl. return line) 
Control terminal 
FT700A 
B3R051 (Parallel indicator panel) 
E3I040 (LON module) 
Printer