40 
Siemens Building Technologies
 
 007836_a_en_--.doc
Fire & Security Products 
 
03.2004
 
 
17 Control 
modules 
17.1  Application of control modules 
 
 
Activation of fire control installations (shutting-down ventilation, closing fire 
dampers etc.) 
 
Activation and monitoring of alarm device 
 
Activation and monitoring of remote transmission equipment 
 
Activation of Mimic Display panels 
17.1.1  Overview of the available modules with control outputs 
 
Modules Monitored 
con-
trol lines 
For alarm devices
Driver outputs 
Programmable 
Contact outputs 
(Volt free) 
Programmable 
Remote transmis-
sion interface 
To remote transmis-
sion equipment 
E3G070 
2 7    
1) 2)
 
 
 
E3L020   16    
1)
 
 
 
E3G050  
 
 
E3G060 
6    
5)
 
 
 
 
K3R072  
48    
3)
 
 
 
K3G060  
 24 NO contact  
4)
 
 
K3I110  
 
16 NO contact  
5)6)
 
 
Can also be used as control inputs (e.g. 'acknowledgement') 
These inputs/outputs also serve for the activation of the remote transmission 
equipment 
For activation of Mimic Display panel, connected to the operating terminal 
B3Q700 or K3I050 (no I-Bus module) -> Details see chapter 17.7 
Applicable only with K3R072 -> Details see chapter 17.9 
5 Programmable 
LON-Bus module -> Details see chapter 18.5 
17.2  Means of linking 
 
 
Any statuses of entry nodes can be linked to control ZONES 
 
Normally, only 1 control ELEMENT is contained in 1 control ZONE (= control 
output) 
 
A user text is allocated to each control ZONE 
E3G050
K3I110
E3L020 
E3G070
E3G060
Acquisition level
Control level
AREA
SECTION
ZONE
Operating level
Acknowledgement circuit
not
monitored
monitored
addressable
collective
Statuses:
- alarm
- info
- switched off
- on detector TEST
- fault
- etc.
Control
ZONE
Operatable functions:
- switch on/off
- activate/de
-activate
Visible statuses:
- active
- switched off
- executed ('Acknowledgem.')
- fault
Digital input 
 
‘active’