Siemens FC700A User Manual

Page of 70
Power supply 
52 
Siemens Building Technologies
 
 007836_a_en_--.doc
Fire & Security Products 
 
03.2004
 
 
22 Power 
supply 
22.1 Concept 
 
The power supply for the FC700A fire detection system consists of: 
 
Converter 
 
(mains voltage -> system voltage 29,6V) 
 
Battery charging unit  (by means of E3C011) 
 
Batteries (lead)  
(capacity as required) 
22.2 Special 
functions 
 
– 
Automatic battery load test 
– 
Battery charging characteristic can be programmed according to make 
22.3 Application 
 
– 
Determine required battery capacity individually -> see chapter 23 
– 
Max. 27Ah per battery charging unit (> 27Ah = auxiliary power supply) 
– 
Parallel operation of several battery charging units possible 
– 
Battery lead without EMI-protection (battery cannot be mounted separately) 
22.4  Power supply for the control unit 
 
 
Battery charging module E3C011 required 
I-Bus
Mains
E3C011
Batteries
AX12..
B3Q700
29,6V
FC
TF*
B2F020
40...220VA
 
22.5 Auxiliary 
power 
supply 
 
* TF = Temperature sensor for battery temperature monitoring
Mains
Basic emergency
power supply
Extension
FT
B2F020
TF*
TF*
C-Bus
Batteries
AX12..
Batteries
AX12..
Monitoring via HW monitoring path
FC
Mains
B2F020
E3C011
E3C011
24V
Battery charging 
unit