Alarm concept 
56 
Siemens Building Technologies
 
 007836_a_en_--.doc
Fire & Security Products 
 
03.2004
 
 
24 Alarm 
concept 
 
 
The alarm concept must be worked out individually for each system 
 
The important thing is to pass on the alarm message quickly to the appropriate 
group of recipients 
The requirements vary between 
– 
'Discreet alerting' of the reconnaissance squad, e.g. via staff paging system 
– 
'Alarm / evacuation' for people familiar with the location 
– 
'Alarm / evacuation' for people unfamiliar with the location 
– 
'Area evacuation', e.g. building storey 
24.1  Cerberus Alarm Concept (CAC) 
 
 
The Cerberus alarm concept prevents the unnecessary turnout of the fire de-
partment for minor incidents 
 
The CAC is based on an alarm organization involving the presence or absence 
of personnel: 
– 
Presence of operating personnel or "Day" 
– 
Absence of operating personnel or "Night" 
 
The response of the operating personnel is monitored by two independent time 
circuits  (V1 and V2) monitored 
 
The CAC is an integrated part of the FC700A control unit. The required parame-
ters can be entered via the user functions 
24.2  Principle of the Cerberus alarm concept 
 
– 
During the "Day" operating mode, if an alarm is activated its source is located 
and the decision is taken "Emergency" or "Minor incident" 
– 
During "Night" operating mode, all signals immediately generate a  "Remote 
alarm" 
– 
The activation of a manual call point always immediately generates a "Remote 
alarm" 
 
F
Alarm
event
Remote
alarm
manned
Operating mode
manned or
unmanned
<Reset> pressed
'Minor incident'
<Acknowledge>
pressed
F
pressed
'Emergency'
Normal
operation
V1
running
V1 = 0
V2 = 0
unmanned
V2
Local
alarm
running
General
alarm
<Alarm delay OFF>
- or -