3
 INSTALLATION 
22 
SITRANS FX300
www.siemens.com/flow
06/2009 - SFIDK.PS.050.F2.02   A5E02100423
3.4.3  Pipelines with control valve
3.4.4  Preferred mounting position
INFORMATION!
To ensure smooth and correct measurement, the manufacturer recommends not installing the 
measuring device downstream from a control valve. This would run the risk of vortex formation, 
which would distort the measuring result.
Figure 3-4: Pipeline with control valve
1  Recommended: installing the device upstream
upstream
upstream
upstream from the control valve at a distance of ≥ 5 DN
2  Not recommended: Installing the flowmeter directly downstream
directly downstream
directly downstream
directly downstream of control valves, due to vortex formation.
Preferred mounting position
1  Above a horizontal pipe
2  underneath a horizontal pipe (not permitted with lines at risk for condensate )
3  On a vertical pipe
INFORMATION!
Depending on the installation position, you may have to rotate the display and/or the connection 
housing. For further information refer to Turning the display on page 24
.