CONFIGURATION PROCEDURE 
Page:  34 
MODULE 
ADDRESS 
LOCATION 
SENTRY 
CHANNEL 
GAS 
TYPE 
LOW 
HIGH 
LATCH 
SCALING 
FACTORS 
SENSOR  
SERIAL # 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 4-1 
System Configuration Worksheet 
NOTES 
Module Address 
Dip switch setting for each sensor module 
Location 
Describe the physical location of the module 
Sentry Channel 
Log the channel number to which the module is wired 
Gas 
Log the name of the gas which is to be detected 
Low Alarm 
Enter the value for the low alarm 
Default values are:  H
2
S: 10 PPM, Combustible 20% LEL, Oxygen 19.5%, Toxic 10 PPM 
High Alarm 
Enter the value for the high alarm 
Default values are:  H
2
S: 20 PPM, Combustible 60% LEL, Oxygen 16.5%, Toxic 20 PPM  
Note:  Combustible Alarms cannot be set greater than 60% LEL. 
7. 
Latch L?/H? 
Determine if any module will require a latching alarm and  write "Y" in the appropriate 
position (e.g.: N/Y indicates a non-latching low alarm and latching high alarm, Y/Y 
indicates both relays will be latching).  The system "defaults are N/Y.   
Note:  Combustible High Alarms are Latching Only
 
Factors 
For H2S (5100-01):  Record the three (three digit) numbers which are written on the sensor  
connector on each sensor. 
For Combustibles:  If the gas to be detected and the gas to be used for calibration are the 
same write "100".   
If the calibration gas is methane and a different gas is to be detected select the correct factor 
from XXXXX.   
Note:  Combustible Gas Scaling Factors are not FMRC approved. 
No factors are required for Oxygen or Toxic sensors. 
Sensor Serial Number 
Record the serial number from the label on the connector of each sensor