CONFIGURATION PROCEDURE 
Page:  35 
4.3  CONFIGURATION INSTRUCTIONS 
Sentry controllers which are components of complete systems 
are factory configured and generally do not require changes 
prior to being placed in service. 
Sentry controllers which have not been factory configured can 
be placed into operation with default values for all configuration 
parameters by using the diagnostic code “0021” described in 
Section  8.3 of this manual. 
The following are step-by-step configuration instructions which 
can be used to customize the operation of the controller for 
specific applications.  After initial configuration the controller 
can be placed in service or used for training as described in the 
this section. 
If an error is made, or suspected, press the RESET key until the 
display reads <RESET SYSTEM> and then press the ENTER 
key, the system will reset and the set-up routine can be re-
started. 
STEP 
KEY 
LOWER DISPLAY 
RESET 
<RESET ALARMS> 
RESET 
<RESET SYSTEM> 
ENTER 
SYSTEM RESET COMPLETE 
 
 
<UNCALIBRATED> 
 
 
Displays continue cycling through each 
module number. Power light changes from 
flashing to solid. 
MODE 
<CALIB/CHANGE> 
ENTER 
CHANGE MODE SELECTED 
Note that if a user entry code has  been 
initiated it must be input here. 
Change/Calibrate light turns on. 
 
 
READ INSTRUCTION MANUAL FIRST  
 
 
PRESS ENTER TO CALIB ALL [GGGG] 
Where GGGG is the gas type. 
MODE 
<CHANGE CALIB> 
MODE 
<CHANGE MODULE> 
ENTER 
USE ARROWS/ENTER 
 
 
MODULE # = 1 
ENTER 
GAS TYPE :  GGGG   
10 
ENTER 
# 1 GGGG IS: ON 
11 
ENTER 
LO ALM:  NONLATCH 
Use arrows to change. 
12 
ENTER 
HI ALM:  LATCH 
Use arrows to change. 
13 
ENTER 
HIGH ALARM = XX 
Use arrows to change each digit. 
14 
ENTER 
LOW ALARM = XX 
Use arrows to change each digit. 
STEP 
KEY 
LOWER DISPLAY 
15 
ENTER 
FACTOR =  100 
Linearizing factors are required for sensor 
modules 5100-01 (H
2
S) . 
Scaling factors can be used for sensor 
module 5100-02 (Combustibles) 
16 
ENTER 
MODULE # = 2 
Repeat steps 9 through 15 for each module. 
17 
MODE 
<SET USER CODE> 
18 
MODE 
<CHANGE PRINTER> 
or 
<CHANGE MODBUS> 
Displays only if printer or MODBUS 
option is installed. 
19 
MODE 
CHANGE GAS TAG 
20 
MODE 
CHANGE MOD TAG 
21 
MODE 
CHANGE ENG UNITS 
22 
MODE 
<OPERATE MODE> 
23 
ENTER 
OPERATE MODE SELECTED 
24 
TIME 
<CHECK HISTORY> 
25 
TIME 
<HISTORY REPORT> 
For printer option only. 
26 
TIME 
<SYSTEM REPORT> 
For printer option only. 
27 
TIME 
<STATUS REPORT> 
For printer option only. 
28 
TIME 
<SET DATE & TIME> 
29 
ENTER 
D&T MM/DD  HH:MM 
Set each digit using the arrows, then 
ENTER to advance to the next digit. 
28 
RESET 
H2S        PPM 
Display will scan through all active gas 
sensor modules. 
4.4  SENTRY TRAINING 
After the controller is configured use this section in conjunction 
with the Sentry 
MENU
Table 
4-2, and Sentry 
FLOWCHARTS, Figure 4-3 through Figure 4-7 to develop an 
understanding of keyboard operation. 
To begin, press the  RESET key until the lower display reads 
PRESS ENTER TO RESET SYSTEM then press  ENTER.  
The system is now in "normal operate mode". The Sensor/Level 
display will cycle through each of the module numbers 
(CONTINUOUS  SCAN). If any module is indicated as 
MODULE OFF use steps 9 through 15 of Section  4.3 to turn 
that module ON.