SERVICE
 
Page:   69 
7.5 
COMBUSTIBLE GAS SENSOR MODULE 
(5100-02) 
7.5.1  DESCRIPTION 
The Combustible Gas Module includes the sensor 
and electronic  assembly installed in an explosion 
proof housing.  The sensor screws into one hub of 
the enclosure and plugs into the bottom electronics 
card via a six pin connector.  Cabling to the 
controller connects to a three pin spring loaded 
terminal strip.  
7.5.2  TROUBLE ANALYSIS 
Electrical adjustment, or replacement of the sensor 
will be necessary under the following conditions: 
• 
Controller displays the following error 
messages: 
CHK BRIDGE VOLT 
SENSOR FAILURE 
LOW SENSITIVITY
 
• 
False readings or alarms are received 
due to sensor inaccuracy. 
Warning: : During sensor adjustments the 
concentration reading on the controller will be 
inaccurate and alarm level concentrations may be 
displayed.  If false activation of the alarm relays 
will cause a problem disconnect the relay wiring 
prior to adjustment or turn the module off using 
the 
CHANGE MODULE
 mode. 
NOTE 
Although all the necessary data can be collected with a 
voltmeter at the sensor module, some helpful 
information can be displayed or printed.  See diagnostic 
codes 0004 and 0008 in Appendix C. 
7.5.3  ADJUSTMENT PROCEDURE 
Prior to reading voltages and making adjustments perform 
a visual inspection to confirm that there are no physical 
problems such as water in the electronics enclosure, 
wiring damage or corrosion. 
Use  Figure  7-6 to locate test  points during the following 
procedures: 
Caution:  The area must be free of flammable vapors or 
gases during any adjustments or maintenance procedures. 
7.5.3.1  BRIDGE VOLTAGE ADJUSTMENT 
Confirm that no combustible gas is present and remove 
sensor module cover. 
Comparing to the "GND" (ground) test point measure 
"BRIDGE VOL" (bridge voltage) and adjust to 2.00 VDC 
using "BRIDGE ADJ" potentiometer.  Turn counter-
clockwise to increase. 
7.5.3.2  ZERO ADJUSTMENT 
Comparing to ground measure 
SIGNAL OUT
 and adjust to 
0.18 VDC by turning 
ZERO ADJ
 potentiometer.  Turn 
counter clock-wise to increase. 
7.5.3.3  SPAN ADJUSTMENT 
1.  Determine the concentration of the calibration 
gas (CG) in % LEL. 
2.  Use the following formula to determine the 
response to the calibration gas at 
SIGNAL OUT
Voltage (Signal Out) = (CG+12)/60 
For Example:  
If CG  = 50% L.E.L 
Signal Out = (50+12)/60 
= 1.03 volts 
 
Figure 7-6 
Cover Plate - Combustible Gas Module