STATE
MIN
NOM
MAX
COMMENTS
Charger High
28.05
28.125
28.20 Adjust with pot
Charger Low
26.40
26.57
26.75
Battery Low
24.15
24.33
24.55
Standby Off
21.5
22.0
22.5 For voltage falling
Notes:
1.   All voltages stated in VDC at temperature of 20
°
C.
2.   Apply temperature compensation of -36 mV/
°
C for temperature deviation from 20
°
C.
3.   This applies also to charger voltage 27.3 VDC.
4.   There are thermal delays, therefore if checking or adjusting in field ensure unit has been
       running for some hours.           
5.  Standby Relay is normally energised (on), and turns off for Battery fail.
TABLE 3.3.2
BATTERY AND CHARGER MONITORING VOLTAGE SPECIFICATIONS
3.3.3 BATTERY
Battery Voltage
:
24Vdc nominal (2 x 12Vdc)
Compatible Makes
Sonnenschein A200 & Sonnenschein A300 series
Powersonic PS12 series
Yuasa NP series
Capacity
:
6 to 50 Ahr
(dependent on configuration)
Space (mm)
:
- Standard Cabinet
  Up to 220H, 440W, 175D (Iss B cabinet)
 
- Small Cabinet
  Up to 200H, 185W, 175D (3 modules fitted)
  Up to 200H, 370W, 125D (4 modules fitted)
  (Refer to Fig 2.2.2)
Battery Test Load
:
46 Ohm nominal. Suitable for 6 Ahr battery (with quiescent
current)
Provision for fitting extra resistors
NOTE:
BATTERY TEST RESISTORS (R52, R53) MUST BE REMOVED FOR NEW 
ZEALAND OPERATION.
3.3.4 FUSES
Location
:
MAF/PSU PCB
Number
Name
Size
Rating
Type
F1
+VBF1
5 x 20mm
2A
Glass Cartridge, Std
F2
+VBF2
5 x 20mm
6A
Glass Cartridge, Std
F3
+VNBF
5 x 20mm
2A
Glass Cartridge, Std
F4
+VE
5 x 20mm
2A
Glass Cartridge, Std
F5
Mains In
5 x 20mm
6A
Glass Cartridge, Std
F7
+VBELLS
5 x 20mm
2A
Glass Cartridge, Std