John Deere Products & Services Portable Generator DCA70SSJU4i User Manual

Page of 120
page 36 — dca70ssJu4i 60 hz generator • operation and parts manual — rev. #2 (04/09/14) 
GeNeratOr start-Up prOCeDUre (MaNUaL MODe)
1.  Place the 
main, g.F.c.i., and aux. circuit breakers 
(Figure 40) in the 
OFF position prior to starting the 
engine.
Figure 40. Main, Aux. and GFCI  
Circuit Breakers (OFF)
2.  Make sure the 
voltage change-over board has been 
configured for the desired output voltage.
3.  Connect the load to the 
receptacles or the output 
terminal lugs as shown in Figure 13. These load 
connection points can be found on the output terminal 
panel and the output terminal panel’s hard wire hookup 
panel. 
4.  Tighten terminal nuts securely to prevent load wires 
from slipping out.
5.  Close all engine enclosure doors (Figure 41).
Figure 41. Engine Enclosure Doors
starting (manual)
1.  Place the 
Auto-Off/Reset Manual Switch in the 
manual position to start the engine (Figure 42).
Figure 42. 
Auto-Off/Reset
  Manual;Switch  
(Manual Position)
INCORRECT
CORRECT
2.  Once the engine starts, let the engine run for 1-2 
minutes (let engine idle longer in cold weather 
conditions). Listen for any abnormal noises. If any 
abnormalities exist, shut down the engine and correct 
the problem. 
3.  The generator’s frequency meter (Figure 43) should be 
displaying the 60 cycle output frequency in 
hertz.
Figure 43. Frequency Meter
4.  The generator’s AC-voltmeter (Figure 44) will display 
the generator’s output in 
volts. If the voltage is not 
within the specified tolerance. 
Figure 44. Voltmeter
5.  Use the voltage adjustment control knob (Figure 45) 
to increase or decrease the desired voltage.
Figure 45. Voltage Adjust Control Knob
NOTICE
If engine fails to start in a specified number attempts, 
the shutdown lamp will illuminate and the Auto-Off/
Reset Switch must be place in the Off/Reset position 
before the engine can be restarted.
NOTICE
Engine will pre-heat automatically in cold weather 
conditions." Glow Plug Hold " message will be displayed 
and the engine will start automatically after pre-heating.