page 38 — dca70ssJu4i 60 hz generator • operation and parts manual — rev. #2 (04/09/14) 
GeNeratOr start-Up prOCeDUre (aUtO MODe)
starting auto mode
  daNgeR
Before connecting this generator to any 
building’s electrical system, a 
licensed 
electrician must install an isolation 
(transfer)  switch. Serious damage to 
the building’s electrical system may occur 
without this transfer switch.
  caution
When connecting the generator to a isolation (transfer) 
switch, 
alWaYs have power applied to the generator’s 
internal battery charger. This will ensure that the engine 
will not fail due to a dead battery.
NOTICE
When the generator is set in the 
aUTO mode, the 
generator will 
automatically start in the event of 
commercial power falling below a prescribed level 
by means of a contact closure that is generated 
automatically by a transfer switch.
  Warning
When running the generator in the 
aUTO mode, 
remember the generator can start up at any time without 
warning. 
never attempt to perform any maintenance 
when the generator is in the auto mode.
  caution
The engine speed switch 
must be set to the “High” 
position when running in the 
auto-start mode. Failing 
to set the switch in the proper position can result in 
damage to your generator when it turns on.
NOTICE
When the 
Auto Off/Reset Manual switch is placed 
in the 
aUTO position, the engine glow plugs will be 
warmed and the engine will start automatically.
When starting generator in 
aUTO mode use the “Manual 
Start-up” procedure except where noted (see below).
1.  Perform steps 1 through 5 in the Before Starting section 
as outlined in the Manual Starting Procedure.
2.  Place the 
auto off/reset manual switch (Figure 53) 
in the 
aUTO position.
Figure 53. 
auto off/reset manual
 Switch (AUTO)
3.  Continue operating the generator as outlined in the 
Manual Start-up procedure (start at step 3).