Moeller Marine XI/OC SIGNAL MODULES 05/02 AWB2725-1452GB User Manual

Page of 38
05/02 AWB2725-1452GB
25
Digital output modules
Transistor output modules
Type
XIOC-8DO
XIOC-16DO
XIOC-16DO-S
Output type
Transistor output (source type)
Transistor output (source type)
Transistor output (source type)
Output voltage
12/24 V DC (+20 %, –15 %)
12/24 V DC (+20 %, –15 %)
12/24 V DC (+20 %, –15 %)
Switching current, minimum
1 mA
1 mA
1 mA
Leakage current
0.1 mA
0.1 mA
0.1 mA
Maximum load current
Per circuit
0.3 A
0.3 A
0.8 A
Per common potential 
terminal
2.4 A
4 A
5 A
Output signal delay
OFFl ON 
F 0.3 ms
F 0.3 ms
F 0.3 ms
ON l OFF
F 1 ms 
F 1 ms 
F 1 ms 
Number of output channels
8 channels/module
16 channels/module
16 channels/module
Number of channels with 
common reference potential
8
16
16
Overvoltage protection
Diode
Diode
Integrated
Fuse
1)
4 A
8 A
None
Electrical isolation
Through optocouplers
Through optocouplers
Through optocouplers
Output indication
By LED (green)
By LED (green)
By LED (green)
External connection
Plug-in terminal block
Plug-in terminal block
Plug-in terminal block
Internal current consumption 
(5 V DC)
 Typ. 30 mA
Typ. 50 mA
Typ. 50 mA
External supply voltage
2)
 
12/24 V DC (+20 %, –15 %);
max. 30 mA
3)
12/24 V DC (+20 %, –15 %);
max. 30 mA
3)
12/24 V DC (+20 %, –15 %);
max. 30 mA
3)
Weight
0.16 kg
0.16 kg
0.16 kg
Short-circuit protection
Yes
1) A blown fuse must not be replaced by the user.
2) Attach the external supply voltage (12/24 V DC) to the “C” and “S” terminals.
3) Internal current consumption of the module.
Figure 30:
Terminal assignment
+12/24 V 
H
0 V 
H
0
1
2
3
4
5
6
7
C
8
9
10
11
12
13
14
15
S
XIOC-16DO(-S)
XIOC-8DO
XIOC-16DO(-S)